background image

www.pulsar.pl                                                               HPSB2548C                                               

GREEN POWER

 

 

 

5

 

W

H

D

- AUX diode indicating DC 27,6V power status at 
the switch mode PSU output  

- green, normal status 

– on, failure: off  

 
Mechanical parameters (tab. 3) 

Enclosure dimensions 

400 x 350 x 90 x8  [mm] (WxHxD) 

Fixation 

See figure 2 

Fitting battery 

2x17Ah/12V (SLA) max. 
370 x 170 x 85mm (WxHxD) max 

Net/gross weight 

3,60 / 3,90 kg 

Enclosure  

Steel plate DC01, thickness: 0,7mm, colour: RAL 9003 

Closing 

Cheese screw x 2 (at the front), (lock assembly possible) 

Connectors 

Power-supply: 

Φ0,63-2,50 (AWG 22-10) 

Outputs: Φ0,63-2,50 (AWG 22-10) 
Battery output BAT: 6,3F-2,5  
TAMPER output: wires, 30cm  

Notes 

The enclosure does not touch the assembly surface so that cables can be led. 
Convectional cooling. 

     

Operation safety (tab.4) 

Protection class PN-EN 60950-1:2007 

I (first) 

Protection grade PN-EN 60529: 2002 (U) 

IP20 

Electrical strength of insulation: 
- between input input and output circuits of the PSU (I/P-O/P) 
- between input circuit and PE protection circuit (I/P-FG) 
- between output circuit and PE protection circuit (O/P-FG) 

 
3000 V/AC min. 
1500 V/AC min. 
  500 V/AC min. 

Insulation resistance: 
- between input circuit and output or protection circuit 

 
100 MΩ, 500V/DC  

Operating parameters (tab.5) 

Environmental class 

  II 

Operating temperature 

-

10ºC...+40ºC (see: chart 1) 

Storage temperature 

-20

ºC...+60ºC 

Relative humidity 

20%...90%, without condensation 

Vibrations during operation 

unacceptable 

Impulse waves during operation 

unacceptable 

Direct insulation 

unacceptable 

Vibrations and impulse waves during transport 

According to PN-83/T-42106 

 

 

Chart 1. Acceptable output current from the PSU depending on ambient temperature. 

 
 
 
 
 
 
 

 

Summary of Contents for Green Power HPSB 2548C

Page 1: ...HPSB 2548C v 1 0 HPSB 48V 2 5A 2x17Ah Buffer switch mode power supply unit EN Edition 1 from 05 01 2016 Supersedes edition...

Page 2: ...2 Installation procedure 3 Operating status indication 3 1 LED indication of operating status 4 Operation and use 4 1 Overload or short circuit of the PSU output SCP on 4 2 Disconnection of discharged...

Page 3: ...The module of the switch mode PSU 2 L N power supply connector 230V AC PE protection connector 3 LED light indicating correct operation of the switch mode PSU 4 Power supply output AUX 5 DCDC boost co...

Page 4: ...efer to chart 1 Ripple 100mV p p max PSU current consumption 90 mA Battery charge current 0 5A max 2x17Ah 5 Short circuit protection SCP F3 15A melting fuse in case of a failure fuse element replaceme...

Page 5: ...ing Operation safety tab 4 Protection class PN EN 60950 1 2007 I first Protection grade PN EN 60529 2002 U IP20 Electrical strength of insulation between input input and output circuits of the PSU I P...

Page 6: ...w valid standards and regulations 2 2 Installation procedure 1 Before installation cut off the voltage in the 230V power supply circuit 2 Mount the PSU in a selected location and connect the wires 3 C...

Page 7: ...t requires disconnecting the output load for the period of approx 1 minute In the case of short circuit of the PSU output the FAUX F3 15A fuse becomes permanently damaged Restoration of voltage at the...

Page 8: ...hin 14 days from the delivery to the service centre of the manufacturer 6 The repair period mentioned in item 5 may be prolonged if there are no technical possibilities to carry out the repairs or if...