background image

www.pulsar.pl                                                               HPSB2548C                                               

GREEN POWER

 

 

 

4

 

 

Fig.2. The view of the PSU. 

1.4 Technical parameters:  

- electrical parameters (tab.2) 
- mechanical parameters (tab.3) 
- operation safety (tab.4) 
- operation parameters (tab.5) 

      

Electrical parameters (tab. 2) 

PSU type 

A (EPS - External Power Source) 

Mains supply 

176÷264V AC 

Current up to 

1,4A@230V AC max.  

Power frequency 

50Hz  

Supply power 

135W max.  

Efficiency 

82% 

Output voltage 

48VDC (+/- 1V)

 

Output current t

AMB

<30°C 

2,5A + 0,5A battery charge - refer to chart 1 

Output current t

AMB

=40°C 

1,7A + 0,5A battery charge- refer to chart 1 

Ripple 

100mV p-p max. 

PSU current consumption 

90 mA

 

Battery charge current 

0,5A max. @ 2x17Ah (

± 5%) 

Short-circuit protection SCP 

F3,15A- melting fuse (in case of a failure, fuse-
element replacement required) 

Overload protection OLP 

110-150% PSU power, manual restart (the fault requires 
disconnection of the DC output circuit) 

Battery circuit protection SCP and reverse  
polarity connection 

melting fuse F15A

 

Surge protection 

varistors 

Excessive discharge protection UVP 

U<19V (

± 5%) – disconnect of connection battery  

Sabotage protection: 
- TAMPER output indicating enclosure opening 

 
- microswitch, NC contacts (enclosure closed), 
0,5A@50V DC (max.) 

LED indication:  
- AC diode indicating AC power status 

 
- red, normal status 

– on, failure: off 

Summary of Contents for Green Power HPSB 2548C

Page 1: ...HPSB 2548C v 1 0 HPSB 48V 2 5A 2x17Ah Buffer switch mode power supply unit EN Edition 1 from 05 01 2016 Supersedes edition...

Page 2: ...2 Installation procedure 3 Operating status indication 3 1 LED indication of operating status 4 Operation and use 4 1 Overload or short circuit of the PSU output SCP on 4 2 Disconnection of discharged...

Page 3: ...The module of the switch mode PSU 2 L N power supply connector 230V AC PE protection connector 3 LED light indicating correct operation of the switch mode PSU 4 Power supply output AUX 5 DCDC boost co...

Page 4: ...efer to chart 1 Ripple 100mV p p max PSU current consumption 90 mA Battery charge current 0 5A max 2x17Ah 5 Short circuit protection SCP F3 15A melting fuse in case of a failure fuse element replaceme...

Page 5: ...ing Operation safety tab 4 Protection class PN EN 60950 1 2007 I first Protection grade PN EN 60529 2002 U IP20 Electrical strength of insulation between input input and output circuits of the PSU I P...

Page 6: ...w valid standards and regulations 2 2 Installation procedure 1 Before installation cut off the voltage in the 230V power supply circuit 2 Mount the PSU in a selected location and connect the wires 3 C...

Page 7: ...t requires disconnecting the output load for the period of approx 1 minute In the case of short circuit of the PSU output the FAUX F3 15A fuse becomes permanently damaged Restoration of voltage at the...

Page 8: ...hin 14 days from the delivery to the service centre of the manufacturer 6 The repair period mentioned in item 5 may be prolonged if there are no technical possibilities to carry out the repairs or if...

Reviews: