www.pulsar.pl                                                      POE084824B   

GREEN POWER CCTV PoE

 

 

 

      

Safety of use (Table 5). 

Protection class PN-EN 60950-1:2007 

I (first) 

Protection grade PN-EN 60529: 2002 (U) 

IP20 

Insulation electrical strength: 
- between input (network) circuit and the output circuits of the PSU (I/P-O/P) 
- between input circuit and PE protection circuit  (I/P-FG) 
- between output circuit and PE protection circuit (O/P-FG) 

 
3000V/AC min. 
1500V/AC min. 
  500V/AC min. 

Insulation resistance: 
- between input circuit and output or protection circuit 

 
100 MΩ, 500V/DC  

 
Operation parameters (Table 6). 

Operating temperature 

-

10ºC...+40ºC (see Figure1) 

Storing temperature 

-

20ºC...+60ºC 

Relative humidity  

20%...90%, no condensation 

Vibrations during operation  

unacceptable 

Surges during operation 

unacceptable 

Direct insolation 

unacceptable 

Vibrations and surges during transport 

According to the PN-83/T-42106 standard 

 

 

Diagram 1. Maximum permissible output current depending on ambient temperature. 

 
2.  Installation. 

 

2.1.  Requirements. 

   The  buffer  PSU should  be  mounted  by  a  qualified installer,  holding  relevant  permits  and  licenses  (applicable 

and    required   for    a   given   country)   for    230V/AC    and    low-voltage   installations.  The    unit   should    be  mounted    in  
confined    spaces,    in    accordance    with    the    2nd  environmental    class,    with    normal    relative    humidity  (RH=90% 
maximum, no condensation) and temperature range from -

10°C up to +40°C. The  power  supply  should  operate  in  a  

vertical position in order to provide free and  convectional  air  flow  through ventilating holes of the enclosure.  

 

During normal operation, the total current drawn by the device should not exceed  

I  =  8x0,3A

*

.  Maximum  battery  charging  current  is  0,2A.  Total  current  of  the  receivers                         

+ battery is max 2,6A. 

              The  power  supply  is  designed  for  a  continuous  operation  and  is  not  equipped  with  a  

power-switch.  Therefore,  an  appropriate  overload  protection  in  the  power  supply  circuit  should  be  provided.  Moreover, 
the  user  should  be  informed  how  to  disconnect  the  power  supply  unit  from  the  mains  supply  (usually  by  assigning  an 
appropriate  fuse  in  the  fuse  box).      The  electrical  system  shall  be  made  in  accordance  with  applicable  standards  and 
regulations.  

The  PSU  is  designed  for  10Mbit/s  and  100Mbit/s  Ethernet  network  (so-called  Fast  Ethernet)

.  However,  it  can 

not be used for a 1000 Mbit/s network (so-called Gigabit Ethernet).

 Connections between the power supply and the 

camera  can  be  done  using  UTP-3  cable  (networks  with  data-rates  up  to  10  Mbit/s)  or  UTP-5  cable.  Due  to  the  lower 
resistance wiring, it is recommended (especially at large distances between the power supply and receivers) to use UTP-
5 cable also for networks with data-rates up to 10 Mbit/s.  

 

 

                                                 

*

 

See diagram 1

 

Summary of Contents for GREEN POWER CCTV POE084824B

Page 1: ...POE084824B v 1 0 PoE 54V 8x0 3A 4x7Ah PoE buffer power supply for up to 8 IP camera EN Edition 4 from 25 05 2015 Supersedes the edition 3 from 15 05 2014 GREEN POWER CCTV PoE...

Page 2: ...D optical indication protections SCP short circuit protection OVP overvoltage protection Surge protection Antisabotage protection OLP overload protection Mounting plate for mounting the network switch...

Page 3: ...et network standard are not used for data transmission data transmission uses 1 2 and 3 6 data pairs The PSU can not be used in Gigabit Ethernet networks where all twisted pairs are involved in the tr...

Page 4: ...ble 1 The description of components of the PoE module Fig 2 Components arrangement Fig 3 The view of the PSU Component No Fig 3 Description 1 The module of the switch mode PSU 2 LED light indicating c...

Page 5: ...c current limiting Battery circuit protection SCP and reverse polarity connection melting fuse Overvoltage protection OVP 62 1 72 9V DC Deep discharge battery protection UVP U 37 V 5 disconnecting the...

Page 6: ...vironmental class with normal relative humidity RH 90 maximum no condensation and temperature range from 10 C up to 40 C The power supply should operate in a vertical position in order to provide free...

Page 7: ...nnected to the terminal marked with the symbol in the PSU enclosure Operation of the PSU without the properly made and fully operational shock protection circuit is UNACCEPTABLE It can cause damage to...

Page 8: ...LED Fig 2 component 1 indicates DC voltage at the PoE module input During normal operation DC supply the LED is permanently illuminated No DC no DC voltage at the module input is indicated by turning...

Page 9: ...If the PTC polymer fuses are used disconnect the load from the power supply output for approximately 1 minute to restore output voltage the time needed to cool down the PTC fuse In case of melting fus...

Page 10: ...service centre of the manufacturer 6 The repair period mentioned in point 5 may be prolonged if there are no technical possibilities to carry out the repairs or if the equipment has been conditionally...

Reviews: