FLOWPULSE INSTRUCTION MANUAL
42
PARAMETER
ADDR
OPTIONS
DEF.
NOTES
Calibration Factor
108
1
–
500
100
In percentage terms,
default is 100, for 100%.
Example: 50% would be
half and 200% would
be double the reading.
Pipe Internal
Diameter
110
10
–
3000
15
Expected Pipe Internal
Diameter in units of
millimetres.
Noise Adapt
Threshold
111
500
–
3000
1000
Defines the difference
between the min value
of the trace and the
normal floor before a
trace is considered to
have a raised noise
floor.
Step Response
Mode
113
0 = Off
1 = On
1
When StepResp is off,
no damping bypass will
be performed.
Step Response
Threshold
115
22
–
426
60
The threshold that the
step change size needs
to exceed before
damping bypass is
invoked.
May use diagnostic
trace to adjust this.
Minimum flow
Cutoff
120
250
–
4000
740
This parameter
multiplies the units of
flow by 23 on the
horizontal axis of the
flow trace. E.g. if set to
2300, then the
corresponding flow
index would be 100,
and the FlowPulse will
not report any flow
unless the red(flow)
indicator exceeds 100
on the flow index.