FLOWPULSE INSTRUCTION MANUAL
40
Configuration Parameters
RS485 Communication and Modbus
The default RS485 setting is 19200-8Bit-Noparity-1Stopbit.
P51 allows the Modbus protocol to be turned on and off, and P52 is the
Modbus Slave ID of the FlowPulse.
When using Modbus-RTU, note that the register addressing scheme uses
Base-0 addressing protocol (i.e. there is no offset of 1).
PARAMETER
ADDR
OPTIONS
DEF.
NOTES
Modbus
Mode
51
0 = Not in use
1
ASCII mode not fully
supported yet.
The PC-485 mode
enables FlowPulse PC
interface using RS485.
Modbus protocol
turned off while using
PC-485. Refer to PC
over 485 section in
Chapter 5 for more
information.
Device
Address
52
Unique Address, 1
–
127
126
Modbus Device id
Baud Rate
53
0 = 1200
1 = 2400
3 = 9600
4 = 19200
5 = 38400
6 = 57600
7 = 115200
4
Baud rate for RS485
Parity
54
0 = No parity
1 = Odd parity
2 = Even parity
0
Parity for RS485
Stop Bit
55
1 = One stop bit
2 = Two stop bits
1
Stop bit for RS485