www.pulsar.pl EN54C
RED POWER plus
50
Table 15. Operation parameters.
Environmental class EN 12101-10:2007
1
Operating temperature
-5
o
C÷40
o
C
Storing temperature
-
25ºC...+60ºC
Relative humidity
20%...90%, no condensation
Sinusoidal vibrations during operation:
10
÷50 Hz
50
÷150 Hz
0,1 G
0,5 G
Surges during operation
0,5 J
Direct insolation
unacceptable
Vibrations and surges during transport
According to the PN-83/T-42106 standard
Table 16. Recommended types and sections of installation cables.
Mains supply ~230 V L-N-PE (Table1 [1])
HDGs 3 x 0,75 mm
2
…1,5 mm
2
OMY 3 x 0,75 mm
2
…1,5 mm
2
AUX1, AUX2 output terminals (Table 1 [2])
HLGs 2 x 1,5 mm
2
…2,5 mm
2
Indication inputs/outputs (Table 1 [2])
YnTKSY 1 x 2 x 0,8 mm
2
Linie sygnałowe dodatkowe (opcja z interfejsem Ethernet) FTP 4x2x0,5 kat.5e