Output Parameters
Range
P830 Out Range
This parameter determines the range of the mA output, from the following.
Option
Description
0= Off
mA output disabled.
1= 0 to 20 mA
mA output directly proportional to the
out mode
(
P831
), so if the reading is 0% the output is 0 mA. If the
reading is 100% the output is 20 mA.
2= 4 to 20 mA
(Default)
mA output directly proportional to the
out mode
(
P831
), so if the reading is 0% the output is 4 mA. If the
reading is 100% the output is 20 mA.
3= 20 to 0 mA
mA output inversely proportional to the
out mode
(
P831
), so if the reading is 0% the output is 20 mA. If
the reading is 100% the output is 0 mA.
4= 20 to 4 mA
mA output inversely proportional to the
out mode
(
P831
), so if the reading is 0% the output is 20 mA. If
the reading is 100% the output is 4 mA.
Operation
P831Out Mode
This parameter determines how the mA output relates to what is measured.
By
default,
it operates exactly the same as the display (
P100
), but it can be
set to operate as follows:
Option
Description
0 = Default
mA output relative to
Mode
P100
1 = Distance
mA output relative to
distance
.
2 = Level
mA output relative to
level
.
3 = Space
mA output is relative to
space
.
When fitted with optional display and integral keypad
5 = Volume
mA output is relative to
volume
.