Fig. 4. Electrical diagram of OC outputs.
3.3. Technical outputs
– relay.
If the OC type outputs are not sufficient to control the unit, it is possible to use the AWZ639relay module
changing technical outputs of the OC type to relay type.
Fig. 5. The diagram of connecting the AWZ639 module.
3.4. Standby time.
Battery-assisted operating depends on battery capacity, charging level and load current. To maintain an
appropriate standby time, current drawn from the PSU in battery mode should be limited:
PSU’s name
Output current max.
Output current (in standby
mode for grade 2 EN50131-6,
EN60839-11)
AWZG2-12V2A-B
2 A
0,58A
AWZG2-12V3A-C
3 A
1,41A
AWZG2-12V5A-C
5 A
1,41A
AWZG2-12V5A-D
5 A
3,33A
AWZG2-24V2A-B
2 A
0,58A
AWZG2-24V3A-C
3 A
1,41A
Total current of the rec
battery charging current mustn’t cross maximum current of power supply
3.5. Battery charging time.
The PSU has a battery circuit charged with direct current. The current selection is done with use of the I
BAT
jumpers. The table below shows how long does ittake to charge a (fully discharged) batteryup to min. 80% of its nominal
capacity.
Table 9. Battery charging time up to the capacity of 0,8.
Battery
Charging current
0,2A
0,5A
1A
2A
7Ah - 9Ah
32h
– 36h
13h - 15h
-
-
17Ah - 20Ah
-
28h - 32h
14h - 16h
-
28Ah
-
-
23h
12h
40Ah
-
-
36h
18h