7
PR8
– Increasing the impulse to T1 time – from rising edge.
The „S” triggering signal (rising
edge) immediately activates the "REL"
relay for the T1 time period. Once the
countdown of the T1 time is finished,
the "REL" relay is deactivated.
Another „S” triggering signal during
the countdown of the T1 time will not
affect the countdown until activation of
the
„REL” relay.
PR9
- Increasing the impulse to T1 time
– from rising edge with resetting T1 time.
The „S” triggering signal (rising
edge) immediately activates the "REL"
relay for the T1 time period. Once the
countdown of the T1 time is finished, the
"REL" relay is deactivated.
Another „S” triggering signal during
the countdown of the T1 time (rising
edge) resets and restarts the T1
countdown process.
PR10
- Increasing the impulse to T1 time
– from falling edge.
The „S” triggering signal (rising
edge) immediately activates the "REL"
relay. After a loss of the
„S” signal
(falling edge), the
„REL” relay stays
activated for the T1 time.
Another „S” triggering signal during
the countdown of the T1 time will not
affect the countdown until activation of
the „REL” relay.
PR11
- Increasing the impulse to T1 time
– from falling edge with resetting T1 time.
The „S” triggering signal (rising
edge) immediately activates the "REL"
relay. After
a loss of the „S” signal
(falling edge), the „REL” relay stays
activated for the T1 time.
Another „S” triggering signal during
the countdown of the T1 time (rising
edge) resets and restarts the T1
countdown process after a loss of the
„S” signal.