AWZ333 

 

 

 

 

 

 

 
 

10 

3.3 Technical outputs.

 

 

The  PSU  is  equipped  with  two  independent  indication  outputs,  OC  type  (open  collector).  They  enable 

transmitting the information about no AC power status and system faults.  

 

 

Fig. 6. Electrical diagram of OC outputs. 

 

 

AW – failure output

: an OC type output indicating a PSU failure. In normal state (during correct operation) 

the output connected to the ground, in case of the failure – disconnected.

 

 

BS  -  absence  of  AC  supply  output

:  -  OC  type  output  that  indicates  absence  of  230V  AC  supply.  In 

normal  status,  with  230V  AC  supply,  the  output  is  open.  In  case  of  power  loss,  the  PSU  will  switch  the 
output after a time period set by the Z1, Z2 

 

jumpers (Fig. 7). 

 

 

Fig. 7. Configuration of the jumpers.

 

 
 
 

4. Operation and use. 
 

4.1 Launching the PSU from a battery 
 

Battery-assisted operating time depends on: the battery capacity, charging level and load current. For 

instance, for a typical, fully-charged 17Ah battery and load current of 3A, the maximum safe working time amounts 
to approx. 4h 30 min. 

 

Launching the PSU from a battery

: push the START button on the device’s board and hold for 5 seconds 

 

Finishing the battery-assisted operation

: push the STOP button on the device’s board and hold for  

 

2 seconds. The PSU will disconnect the output after 10 seconds. 

 

4.2 Disconnection of a discharged battery. 

The  PSU  is  equipped  with  the  discharged  battery  disconnection  system  and  discharged  battery  indication. 

During the battery-assisted operation, reducing voltage below ~10V at the battery terminals will trigger a countdown 
to the battery disconnection. The disconnection time period is Z3, Z4 jumper selectable. (Fig.8) 

 

 

Fig. 8. Configuration of the jumpers.

 

 

 

4.3 Dynamic battery test 

The PSU runs a battery test every 10 minutes. It is done by a momentary output voltage reduction and 

voltage measurement at the battery terminals. A failure is indicated when voltage drops below ~12,2V. The battery 
test facility can be switched off if, for instance, the battery is not connected to the PSU. 

 
Deactivating/activating the test: 

while mains supply, press the STOP button on the main board and hold it for 3 

seconds. The device will confirm the activation/deactivation in the following ways: (Tab.8.)  

 

testing off – 12 sounds 

 

testing on –  3 sounds 

 
 
 
 

Summary of Contents for AWZ 333

Page 1: ...AWZ 333 v 2 1 AWZ 13 8V 3A 17Ah LM Linear Buffer Power Supply Unit EN Edition 4 from 16 09 2013 Supercedes the edition 3 from 24 02 2012...

Page 2: ...1 Technical description 1 1 General description 1 2 Principle of operation 1 3 Block diagram 1 4 Description of PSU components and connectors 1 5 Specifications 2 Installation 2 1 Requirements 2 2 In...

Page 3: ...tion of the 230V mains supply the PSU automatically charges up and preserves the battery PSU operating status is indicated by LEDs on the faceplate red LED failure indication additionally failure stat...

Page 4: ...upply output of the battery BAT red BAT black 7 RED DIODE LED indication 8 GREEN DIODE LED indication 9 CHARGE pin 10 AC AC power connector 11 Connectors TAMPER contacts of the sabotage protection swi...

Page 5: ...he view of the PSU 1 5 Specifications electrical specifications tab 3 mechanical specifications tab 4 operation safety tab 5 operating specifications tab 6 Uwy f Io diagram Fig 4 Electrical specificat...

Page 6: ...level 0V microswitch NC contacts enclosure closed 0 5A 50V DC max LED indication LEDs AC DC power status failure Acoustic indication piezoelectric indicator 75dB 0 3m ON OFF function F1 fuse F 5A F2 f...

Page 7: ...iate fuse in the fuse box The electrical system shall follow valid standards and regulations 2 2 Installation procedure Before installation make sure that the voltage in the 230V power supply circuit...

Page 8: ...8mm clamp following the procedure according to Fig 5 put the battery into the enclosure lead the clamp through the left A hole lead the clamp over the up side of the battery lead the clamp through th...

Page 9: ...cause disconnect the load and connect after 30 60 s 4 too high output voltage Uout 14 5V damaged voltage regulator wrong setting of the P1 potentiometer check the setting of the P1 potentiometer 5 PSU...

Page 10: ...g the PSU from a battery push the START button on the device s board and hold for 5 seconds Finishing the battery assisted operation push the STOP button on the device s board and hold for 2 seconds T...

Page 11: ...should be limited Characteristics for a 17Ah 12V SLA for grade 1 12h current Id 1 4A 4 6 PSU overload The PSU is equipped with an output protection due to a PTC polymer fuse If the load of the PSU exc...

Page 12: ...s to carry out the repairs or if the equipment has been conditionally accepted due to the breaking warranty terms by the claimant 7 All the services rendered by force of the warranty are carried out a...

Reviews: