Pulsar ADOC552415 Quick Start Manual Download Page 4

ww.pulsar.pl 

 

 

 

 

ADOC552415 

 
 

 

Fig. 2. The view of the PSU. 

1.4 Specifications: 

- electrical specifications (tab.2) 
- mechanical specifications (tab.3) 
- operation safety (tab.4) 
- operating specifications (tab.5) 

 

 

     Electrical specifications (tab. 2). 

 

Mains supply 

88 ÷ 264V AC 

Current consumption 

1A@230VAC typ.  

PSU power  

53,92W max.  

Efficiency 

74% 

Output voltage 

22V÷ 27,6V DC – buffer operation 
19V÷27,6V DC – battery-assisted operation 

Output current 

1,5A + 0,16A battery charge 

with (18.2CFM fan – see chart 1)

 

Voltage adjustment range 

24÷29V DC 

Ripple voltage 

100 mV p-p max. 

Current consumption by PSU systems 

80 mA  

Battery charging current 

0,16A 

Short-circuit protection SCP  

electronic, automatic recovery 

Overload protection OLP 

105-150% of power supply, automatic recovery

 

Battery circuit protection SCP and reverse 
polarity connection 

fuse 

Surge protection 

varistors 

Over voltage protection OVP 

31,74-37,26V  (automatic recovery) 

Deep discharge protection UVP 

U<20V (± 5%) – disconnection of the battery terminal 

Technical outputs: 
- FAC; output indicating AC power failure 
 
 
 
- FPS; output indicating DC absence/PSU 
failure 
 
- FLB output indicating battery low voltage 
 
 

 
- relay type: 1A@ 30VDC/50VAC, time lag: approx. 10s. 
- OC type, 50mA max., normal status: L (0V) level, failure: hi-Z 
level, time lag: 10s. 
 

- relay type: 1A@ 30VDC/50VAC, 

- OC type, 50mA max., normal status: L (0V) level, failure: hi-Z level  
 

- relay type: 1A@ 30VDC/50VAC, 

- OC type, 50mA max., normal status: (U

BAT

 >11,5V): 

 L (0V) level, 
 failure: (U

BAT

 <11,5V): hi-Z level 

 
 
 
 

Summary of Contents for ADOC552415

Page 1: ...ADOC552415 v 1 0 ADOC 27 6V 1 5A OC Enclosed buffer switch mode power supply unit with automatic operation control EN Edition 1 from 29 10 2013 Supercedes edition ...

Page 2: ...NTENTS 1 Technical description 1 1 General description 1 2 Block diagram 1 3 Description of PSU components and connectors 1 4 Specifications 2 Installation 2 1 Requirements 2 2 Installation procedure 3 Operating status indication 3 1 LED indication of operating status 3 2 Technical outputs 4 Operation and use 4 1 Overload or short circuit of the PSU output 4 2 Battery assisted operation 4 3 Mainte...

Page 3: ...voltage 4 FAC AC absence technical output relay type 5 FPS output indicating DC absence PSU failure relay type 6 FLB output indicating battery low voltage relay type 7 FAC AC absence technical output OC type 8 FPS output indicating DC absence PSU failure OC type 9 FLB output indicating battery low voltage OC type 10 B B battery connector 11 V COM DC supply output 12 L N 230V AC power connector PE ...

Page 4: ...t circuit protection SCP electronic automatic recovery Overload protection OLP 105 150 of power supply automatic recovery Battery circuit protection SCP and reverse polarity connection fuse Surge protection varistors Over voltage protection OVP 31 74 37 26V automatic recovery Deep discharge protection UVP U 20V 5 disconnection of the battery terminal Technical outputs FAC output indicating AC powe...

Page 5: ...60ºC Storage temperature 20ºC 85ºC Relative humidity 20 90 without condensation Vibrations during operation unacceptable Impulse waves during operation unacceptable Direct insolation unacceptable Vibrations and impulse waves during transport PN 83 T 42106 2 Installation 2 1 Requirements The buffer PSU is to be mounted by a qualified installer holding relevant permits and licenses applicable and re...

Page 6: ... protection circuit is UNACCEPTABLE It can cause a device failure or an electric shock 4 Connect load loads to proper output connectors of the power supply positive pole is marked as V negative pole as COM 5 Connect the technical outputs to the central or other device 6 Connect the battery to proper output connectors of the power supply positive pole is marked as B negative pole as B 7 Once the te...

Page 7: ...n case of absence of DC voltage at the output e g short circuit the output is switched into high impedance state hi Z relay output In case of a failure the contacts of the relay change over CAUTION In the Fig 2 the set of contacts shows a potential free status of the relay which corresponds to a state with no DC power PSU failure FLB technical output indicating battery voltage OC type output Under...

Page 8: ...vide warranty repairs at the earliest convenienve however not later that within 14 days from the delivery to the service centre of the manufacturer 6 The repair period mentioned in item 5 may be prolonged if there are no technical possibilities to carry out the repairs or if the equipment has been conditionally accepted due to the breaking warranty terms by the claimant 7 All the services rendered...