7.22 Inhibitor - Inhibitor Feed Mode Menu
From this menu pick the mode that the inhibitor feed will follow.
Pulse Timer
– See the menu for this function in the following section.
Limit Timer
– Set this value to the maximum amount of time you want the inhibitor to
feed while the bleed function is running. If this time is exceeded the controller will go into
alarm and the inhibitor feed control output will de-energize.
Cycle Timer
– Set the inhibitor feed time period and percentage of the time period.
Example: Cycle Time=60minutes, % Minutes to run=10, the inhibitor will feed for 10% of
60 minutes, or 6 minutes every 60 minutes.
%Post Blowdown
– See the menu for this function in the following section.
7.23 Inhibitor - Inhibitor Feed Mode
– Pulse Timer Menu
From this menu configure how you want the inhibitor to feed while in pulse timer mode. This
mode uses the water meter input to cause a counter to accumulate a certain volume of water
before the inhibitor is feed. Once the accumulated volume is reached the inhibitor is feed for the
programmed Feed Time.
Feed Time
– Set this value to the amount of time you want the inhibitor to feed when the
water meter accumulator reaches its target.
Home Screen
Settings
Inhibitor
Feed Time
Accum Set
Accum Count
Back | Select
Inh Feed Mode
Pulse Timer
Home Screen
Settings
Inhibitor
Pulse Timer
Limit Timer
Cycle Timer
% Post Bl’d
Back | Select
Inh Feed Mode