background image

2.3  Piping System 

 

Attention to piping detail will assure an easy startup and long life of your GLM. Please follow these guidelines: 
 

Suction Piping 

Isolation Valve and Unions:  

Isolation valves allow 

the system to be isolated from the process fluid to 
facilitate safe servicing. They also aid in the operation 
of Calibration columns. Valves should include good 
visible indications of open/closed condition. Unions 
assist with installation and maintenance. Valves that 
integrate union fittings are ideal. 

 

Strainer:  

Successful

 

installations always include a 

strainer on the suction side of the pump to exclude 
material that can cause the check valves to 
malfunction or the diaphragm to rupture. Select the 
material, size and mesh to be compatible with the fluid 
type, intended flow rate and service interval. A 100 
mesh screen is generally recommended. 

 

 
Calibration Column (Optional): 

Used to calibrate pump performance. Include an isolation valve and 

vent line back to the supply tank to facilitate safe operation. 
 

Pressure Gage (Optional):

  A pressure gage should be included on the suction side of the pump when 

the suction pressure of the system is unknown or variable. The gage is also a good indicator of Strainer 
maintenance status. 
 

Discharge Piping 

Discharge Pressure Gage: 

Install a pressure gage no less than 2 pipe diameters from the threaded 

fitting on the discharge valve. A discharge pressure gage is critical to confirming proper operation of the 
pump and setting the pressure relief and back pressure valves. 

IMPORTANT:  DO NOT Install an elbow directly into the discharge valve threaded fitting as it will 
create excessive back pressure that can lead to premature diaphragm failure. 

Pressure Relief Valve

: Install a Pressure Relief Valve as close 

to the pump as possible. Using the leg of a T fitting for this 
purpose is acceptable (with the normal discharge taking the 
straight path and the relief flow taking the leg). The relief 
pressure must be set at or below the rated pressure indicated 
on the pumps nameplate. 

NOTE: Failure to install and properly set a 
Pressure Relief Valve can lead to damage of the 
Pumps drive mechanism that will not be covered 

under warranty. 

Back Pressure Valve: 

Install a Back Pressure Valve to 

generate a consistent Back Pressure to the pump for accurate 
operation and to prevent siphoning. 

Pulsation Dampener: 

 Reciprocating diaphragm metering 

pumps only discharge fluid for ½ of a pump cycle. A Pulsation 
Dampener will smooth the associated flow/pressure variation to  
the downstream process. 

 

Figure 3: Discharge P&ID

 

 

Figure 2: Suction P&ID

 

Summary of Contents for GLM1

Page 1: ...PULSA GLM MECHANICAL DIAPHRAGM METERING PUMP Bulletin IOM GLM 5000 Rev A Installation Operation Maintenance Manual Models GLM1 6...

Page 2: ...sense and judgment during all installation adjustment and maintenance procedures 4 Ensure that all safety work procedures and standards that are applicable to your company and facility are followed du...

Page 3: ...put Adjustment 5 3 3 Priming the Reagent Head 5 3 4 Calibration 7 4 MAINTENANCE 7 4 1 Lubrication 8 4 2 Wet End Removal Inspection Reinstallation 9 4 3 Check Valves 11 4 4 Motor Removal Reinstallation...

Page 4: ......

Page 5: ...to operate in an environment where the pump is protected from direct sunlight and precipitation i e under shelter The ambient temperature must be between 32 F 0 C and 104 F 40 C If necessary add envir...

Page 6: ...ndicator of Strainer maintenance status Discharge Piping Discharge Pressure Gage Install a pressure gage no less than 2 pipe diameters from the threaded fitting on the discharge valve A discharge pres...

Page 7: ...ds must not exceed 10 ft lbf 13 5 n m moment or 5 lbf 22 n in any direction When temperature variations are expected provide for thermal expansion and contraction of piping components so that force an...

Page 8: ...rated by the pump This results in a reduction in accuracy and loss of control over the metering process To prevent this flow through condition the discharge pressure must exceed the suction pressure b...

Page 9: ...djustments without releasing the lock may damage the locking mechanism 2 Adjust the knob to the desired output a Read the setting directly from the knob marking where it aligns with the stroke barrel...

Page 10: ...reagent head through the discharge valve port with process or compatible liquid and then reinstall the check valve 6 Start the pump at the 0 stroke length setting and slowly increase the setting to 1...

Page 11: ...e through the points For stable conditions this line should predict settings to attain required outputs Note All users are encouraged to test the flow rate of their pump once installed in their system...

Page 12: ...from the piping system 2 Remove the Vent Fill cap on top of the Gear Box under the motor adaptor lip 3 Locate the Gear Box drain plug at the bottom of the Gear Box under the Stroke Adjustment Knob see...

Page 13: ...ring 2 2 2 4 Reagent Head 1 1 1 5 Diaphragm 1 1 1 6 Front Cover Plate 1 1 1 7 Hex Head Bolt 8 10 12 8 Flat Washer 8 10 12 9 Suction Check Valve Assembly 1 1 1 10 Suction Connection Assembly 1 1 1 11...

Page 14: ...ment 7 Tilt the head and pour out any liquids retained by the check valves into a suitable container continuing to follow safety precautions as appropriate 8 Remove the final bolt and rinse or clean t...

Page 15: ...rsonnel exposure to hazardous materials 4 Close the inlet and outlet shutoff valves 5 Disconnect the suction piping at the suction shut off valve union by releasing the union retaining nut Caution Pro...

Page 16: ...refully the position of the component parts to assist in re assembly 9 Disassemble both valves and check components for wear or damage The seats should have a sharp edge and be free from dents or nick...

Page 17: ...ling should be even with the end of the shaft For the 71 frame motor the coupling should be installed over the shaft up to the collar the end of the shaft will be slightly recessed into the coupling N...

Page 18: ...ross Head the part that the Diaphragm threads onto is fully retracted into the Gear Box 9 Evenly loosen all 4 bolts that retain the Pump Head to the Gear Box Figure 17 Pump Head Retaining Bolt Removal...

Page 19: ...sentative A list of the PULSA GLM KOPkit numbers can also be found on the next page The kit is identified by the model number of the pump the wetted end material and the process connection thread type...

Page 20: ...E 6 Troubleshooting Difficulty Probable Cause Remedy Pump motor does not start Faulty power source Check power source Blown fuse circuit breaker Replace eliminate overload Broken wire Locate and repai...

Page 21: ...sure Water hammer Install pulsation dampener Stroke length at partial setting Some operating noise is characteristic of lost motion pumps Low grease level Add or replace grease Piping noisy Pipe size...

Page 22: ...tall with fluid flow in direction of arrow on valve body Pulsation Dampener A pulsation dampener is a pneumatically charged diaphragm type chamber that intermittently stores hydraulic energy Used on t...

Page 23: ...8 Dimensional Drawing Dimension table in mm inches 19...

Page 24: ...1 160 0 6 3 95 5 3 8 325 12 8 94 5 3 7 37 0 1 5 56C 196 0 7 7 Model Dimension G H J K L M GLM1 GLM2 71 Consult Factory 170 0 6 7 79 0 3 1 91 5 3 6 NPT BSPT TUBING NPT BSPT TUBING 56C 175 0 6 9 103 0 4...

Page 25: ...9 Policies Procedures Reference our Policy Manual at http www pulsa com resources downloads forms 21...

Page 26: ...CHANICAL DIAPHRAGM METERING PUMP Bulletin IOM GLM 5000 Rev A Pulsafeeder Inc A unit of IDEX Corporation 2883 Brighton Henrietta Town Line Road Rochester NY 14623 1 585 292 8000 www pulsa com pulsa ide...

Reviews: