DOWN-THE-WELL INSTALLATION: 

 

Often it is desirable to provide chemical feed 
near the intake of the well pump for 
additional retention time and mixing of the 
chemicals. An additional length of discharge 
tubing will be required for this installation. 
Secure the end of the discharge tubing to the 
pump cylinder, drop pipe, or foot valve and 
lower it into the well. An anti-siphon valve 
must be installed on systems such as this 
where the discharge is lower than the feeder 
and the chemical storage tank.  

Failure to install anti-siphon valve may 
allow siphoning to occur.  

 

 

ANTI-SIPHON VALVE: (optional) 

 

Under any installation condition where the 
possibility of siphoning or suction may occur 
on the discharge side of the pump, install an 
anti-siphon valve on the discharge side of the 
feeder. The anti-siphon valve is not part of 
the standard package. This item can be furnished by your dealer at extra cost.  

 

 

PRESSURE RELIEF VALVE: (optional) 

 

Series 100/150 chemical pumps are rated to pump against a line pressure up to 
100 PSI (7 BAR). If the line pressure on an installation could fluctuate above 100 
PSI (7 BAR), install a pressure relief valve on the discharge side of the pump 
head. Once the pressure reaches a certain level, the pre-set relief valve will 
return the solution being pumped back to the solution tank. This will prevent 
motor burnout or diaphragm rupture. The relief valve is not part of the standard 
package. This item can be furnished by your dealer at extra cost. Read relief 
valve instructions carefully before installing.  
 

 

BLEED VALVE INSTALLATION: (optional) 

NOTE:

 After disconnecting power to the pump and taking necessary safety 

precautions regarding the chemical and system. 
1.  Remove the coupling nut and tubing from the discharge port of the pump. 
2.  Remove the valve housing from the discharge side of the pump head and 

replace it with the .38inch valve housing from the kit (this step is not required 
if the pump is already fitted for .38inch tubing. 

3.  Install the TFE gasket over the discharge fitting. 
4.  Install the bleed valve assembly over the discharge fitting and gasket. 
5.  Install the bypass tubing from the kit into the bypass port of the bleed valve 

and hand-tighten the coupling nut.  Bypass tubing should be connected to 
return bypassed liquid back to the solution tank. 

6.  Install the discharge tubing into the discharge port of the bleed valve and hand tightens the coupling nut. 

Summary of Contents for Chem-Tech 100 Series

Page 1: ...READ ALL CAUTIONS CAREFULLY BEFORE INSTALLING PUMP INSTRUCTION MANUAL P N 32040 Rev C...

Page 2: ...conditioning specialists when treating potable water Always depressurize system prior to installation or disconnecting the metering pump tubing If injection point is lower than the chemical tank and...

Page 3: ...INSTALLING METERING PUMP 1 Chemicals used may be dangerous and should be used carefully and according to warnings on the label Follow the directions given with each type of chemical Do not assume chem...

Page 4: ...TING The carton should contain Metering Pump 4 ft 1 21 m Clear Flexible Suction Tubing 4 ft 1 21 m Stiff White Return Tubing Feeder can be mounted on a wall shelf bracket Figure B tank stand platform...

Page 5: ...manually filled or an approved means must be used to prevent a cross connection between the chemical tank contents and the potable water line Check local plumbing regulations CHEMICAL INJECTION Chemi...

Page 6: ...BAR install a pressure relief valve on the discharge side of the pump head Once the pressure reaches a certain level the pre set relief valve will return the solution being pumped back to the solution...

Page 7: ...ead POINT OF INJECTION Pipe corrosion can result if dillution at the injection point does not occur rapidly This problem is easily prevented by observing this simple rule install injection fitting so...

Page 8: ...site A test for chemical residual in the treated water is the best indication of the correct pump setting MAINTENANCE SCALE GASKETS AND CHECK VALVES When checking the metering pump or providing routi...

Page 9: ...wise Figure O 4 A new pump head or diaphragm should be installed if either is broken or cracked see parts list at the end of this manual The new pump head can be installed by going through the above s...

Page 10: ...head Also chemical incompatibility can cause cracking and subsequent leakage 7 While pump is running turn bleed valve adjustment screw counter clockwise until air is purged Close bleed valve PUMP LOSE...