YR80.242 Installation Manual 

 

 

 

Product Description 

The YR80.242 is a redundancy module for building redundant power supply systems. It is equipped 
with two input channels and one output. The two inputs are decoupled by MOSFET technology.  
 

Intended Use 

This device is designed for installation in an enclosure and is intended for commercial use, such as in 
industrial control, process control, monitoring and measurement equipment or the like. Do not use this 
device in equipment where malfunction may cause severe personal injury or threaten human life.  
The redundancy module can be used with any type of power supply as long as the maximum output 
current ratings are not exceeded. It is suitable for power supplies with continuous overload current as 
well as any kind of intermittent (Hiccup) overload behavior. 
 

Installation Instructions 

Install the device in an enclosure providing protection against electrical, mechanical and fire hazards. 
Do not ground or earth the positive output pole which could prevent redundancy in case of a ground 
failure. Ground the negative output pole, when needed. 
Use only power supplies with a negligible output ripple voltage in the low frequency range between 
50Hz and 10kHz when used in marine applications according to the GL regulations. 
Install the device onto a DIN-rail according to EN 60715 with the input terminals on the bottom of the 
device.

 

Other mounting orientations require a reduction in output current. 

Make sure that the wiring is correct by following all local and national codes. Use appropriate copper 
cables that are designed for a minimum operating temperature of 60°C for ambient temperatures up to 
+45°C, 75°C for ambient temperatures up to +60°C and 90°C for ambient temperatures up to +70°C. 
Ensure that all strands of a stranded wire enter the terminal connection. 
Unused screw terminals should be securely tightened. 
The device is designed for pollution degree 2 areas in controlled environments.

 

No condensation or 

frost is allowed. 
The enclosure of the device provides a degree of protection of IP20. 
The input must be powered from a PELV or SELV source or an “Isolated Secondary Circuit” in order to 
maintain a SELV or PELV output. 
Check correct input polarity. The device will not operate when input voltage is reversed. 
The device is designed as “Class of Protection III” equipment according to IEC 61140. 
A PE (ground) connection is not required. However, connecting the chassis ground terminal to ground 
can be beneficial to gain a high EMI immunity. 
The device is designed for convection cooling and does not require an external fan. Do not obstruct 
airflow and do not cover ventilation grid! 
The device is designed for altitudes up to 6000m (19685ft). See additional requirements in the product 
datasheet for use above 2000m (6560ft). 
Keep the following minimum installation clearances: 40mm on top, 20mm on the bottom, 5mm left and 
right side. Increase the 5mm to 15mm in case the adjacent device is a heat source. When the device 
is permanently loaded with less than 50%, the 5mm can be reduced to zero. Under special 
circumstances clearances can be reduced. See details in the product datasheet. 
The maximum surrounding air temperature is +70°C (+158°F). The operational temperature is the 
same as the ambient or surrounding air temperature and is defined 2cm below the device. 
The device is designed to operate in areas between 5% and 95% relative humidity. 
 

Installation Instructions for Hazardous Location Areas 

The device is suitable for use in Class I Division 2 Groups A, B, C, D locations and for use in Group II 
Category 3 (Zone 2) environments. 
Hazardous Location classification: ATEX: EPS 11 ATEX 1 312 X, II 3G EX ec IIC T4 Gc 
WARNING EXPLOSION HAZARDS! 
Substitution of components may impair suitability for this environment.  
Do not disconnect the device unless power has been switched off or the area is known to be non-
hazardous. 
A suitable enclosure must be provided for the end product which has a minimum protection of IP54 
and fulfils the requirements of the EN 60079-0. 

 

Functional Description 

The device can supply any kind of loads, including unlimited capacitive and inductive loads. 
Do not apply return voltages from the load to the output higher than 40Vdc. 

 
 
 

 

Technical data

 

All values are typical figures specified at 24Vdc input voltage, 80A output 
current, 25°C ambient temperature and after a 5 minutes run-in time 
unless otherwise noted. 

Input voltage DC 

DC 12-28V 

±30% 

Input voltage range 

8.4 –36.4Vdc 

 

Input current DC 

2x 40A 

Below +60°C ambient 

 

2x 30A 

At +70°C ambient 

 

2x 65A 

Up to 5 seconds 

 

Derate linearly b60 and +70°C 

Output current 

80A 

Below +60°C ambient 

 

60A At 

+70°C 

ambient 

 

130A 

Up to 5 seconds 

Maximum output current 
below 6Vdc 

44A R.M.S. 

In any overload or short 
circuit condition 

Input to output voltage loss 65mV 

At 2x 20A input 

 

145mV 

At 2x 40A input 

Power losses 

0.22W 

At no load 

 

2.9W 

At 2x 20A input 

 

11.8W 

At 2x 40A input 

Temperature range 

-40°C to +70°C 

 

Max. wire size (litz wire) 

10mm² Input 

terminals 

Wire size AWG 

AWG 22-8 

Input terminals 

Max. wire diameter 

5.2mm Input 

terminals 

Wire stripping length 

12mm / 0.5inch 

Input terminals 

Tightening torque 

2.3Nm / 20lb.inch

Input terminals 

Max. wire size (litz wire) 

35mm² Output 

terminals 

Wire size AWG 

AWG 20-2 

Output terminals 

Max. wire diameter 

7.6mm Output 

terminals 

Wire stripping length 

18mm / 0.7inch 

Output terminals 

Tightening torque 

2.5Nm / 22lb.inch

Output terminals 

Size (wxhxd) 

46x124x127mm Without 

DIN-rail 

Weight 

370g / 0.81lb 

 

 
 

Functional diagram 

+

-

+

-

+

-

Input 1

control

control

Input 2

Chassis
Ground

Output

 

 

Wiring scheme - 1+1 redundancy 

L

PE

Load

Failure

Monitor

o

p

ti

o

nal

Redundancy

Module

Output

Input

 1

Input

2

+

-

+

-

+

-

Power

Supply

Output

DC-
OK

Input

o o

+

-

+

-

L N

Power

Supply

Output

DC-
OK

Input

o o

+

-

+

-

L N

I

I

N

 

 

Wiring scheme - n+1 redundancy 

L

PE

Failure

Monitor

opt

ion

a

l

Redundancy

Module

Output

Input

 1

Input

2

+

-

+

-

+

-

Power

Supply

Output

DC-
OK

Input

o o

+

-

+

-

L N

Power

Supply

Output

DC-
OK

Input

o o

+

-

+

-

L N

I

I

N

Load

opt

ion

a

l

Redundancy

Module

Output

Input

 1

Input

2

+

-

+

-

+

-

Power

Supply

Output

DC-
OK

Input

o o

+

-

+

-

L N

Power

Supply

Output

DC-
OK

Input

o o

+

-

+

-

L N

I

I

 

Reviews: