SLAD4.100 Installation Manual 

 

 

 

Product Description 

The SLAD4.100 is a DIN-rail mountable DC/DC converter, which provides network power for the AS-
Interface

®

 system. The AS-Interface

®

 system is a field bus technology, where power and data are 

provided by the same single two-conductor wire. Therefore, special DC/DC converters with an 
integrated data-decoupling circuit are required to prevent the modulated signal voltage on the AS-
Interface

®

 bus from being corrupted. 

 

Intended Use

 

This device is designed for installation in an enclosure and is intended for commercial use to supply 
power to AS-Interface

®

 network systems.  

Do not use this device in equipment where malfunction may cause severe personal injury or threaten 
human life.  
When operating without AS-Interface structure (e.g. in a laboratory test), connect a 470

μ

F/35V 

capacitor between AS-Int and AS-Interface – terminals to avoid output voltage oscillations. 
 

Installation Instructions 

Install device in an enclosure providing protection against electrical, mechanical and fire hazards. 
Install the device onto a DIN-rail according to EN 60715 with the input terminals on the bottom of the 
device. 
Make sure that the wiring is correct by following all local and national codes. Use appropriate copper 
cables that are designed for a minimum operating temperature of 60°C for ambient temperatures up to 
+45°C, 75°C for ambient temperatures up to +60°C and 90°C for ambient temperatures up to +70°C. 
Ensure that all strands of a stranded wire enter the terminal connection. Unused screw terminals 
should be securely tightened. 
The device is designed for pollution degree 2 areas in controlled environments. No condensation or 
frost is allowed. 
The enclosure of the device provides a degree of protection of IP20. The housing does not provide 
protection against spilled liquids. 
The input can be powered from batteries or similar DC sources. The continuous voltage between the 
supply voltage and the PE/ground potential must not exceed 60Vdc. The input must be powered from 
a PELV or SELV source or an "Isolated Secondary Circuit" in order to maintain a SELV or PELV 
output. 
Check for correct input polarity. The device will not operate when the voltage is reversed. 
A disconnecting means shall be provided for the input of the device. 
The device is designed as “Class of Protection III” equipment according to IEC 61140. A PE (ground) 
connection is not required. However, connecting the chassis ground terminal to ground can be 
beneficial to gain a high EMI immunity. 
The device is designed for convection cooling and does not require an external fan. Do not obstruct 
airflow and do not cover ventilation grid! 
The device is designed for altitudes up to 2000m (6560ft). 
Keep the following minimum installation clearances: 40mm on top, 20mm on the bottom, 5mm left and 
right side. Increase the 5mm to 15mm in case the adjacent device is a heat source. When the device 
is permanently loaded with less than 50%, the 5mm can be reduced to zero. 
The device is designed, tested and approved for branch circuits up to 50A without additional protection 
device. If an external fuse is utilized, do not use circuit breakers smaller than 10A B- or 8A C-
Characteristic to avoid a nuisance tripping of the circuit breaker. 
The maximum surrounding air temperature is +70°C (+158°F). The operational temperature is the 
same as the ambient or surrounding air temperature and is defined 2cm below the device. 
The device is designed to operate in areas between 10% and 90% relative humidity. 
 

Functional Description 

The output is electronically protected against no-load, overload and short circuit and can supply any 
kind of loads, including inductive and capacitive loads.  
The green DC-OK LED reports a nominal output voltage of a running device. The LED is off as soon 
as the unit is in overload mode. 
Do not parallel devices for higher output currents. 
Do not connect outputs of devices in a series connection for higher output voltages. 
In case of an internal defect, a redundant circuit limits the maximum output voltage to 36V. The output 
shuts down and automatically attempts to restart. 

 

Technical Data

 

All values are typical figures specified at 24Vdc input voltage, 30.6V 4A 
output load, 25°C ambient temperature and after a 5 minutes run-in time 
unless otherwise noted. 

Output voltage 

DC 30.6V 

Nominal 

Adjustment range 

Not adjustable 

Factory setting 30.6V 

Output current 

4A 

Below +60°C ambient  

 

3A At 

+70°C 

ambient 

 

Derate linearly b60°C and +70°C 

 

For use on AS-Interface

®

 networks only 

Current limitation 

>4.4A  

Input voltage 

DC 24V 

-25% / +35% 

Input current 

5.50A  

Input inrush current 

1.2A pk 

Temperature 
independent 

Efficiency 

90.5%  

Power losses 

12.7W  

Hold-up time 

6ms  

Temperature range 

-25 to +70°C 

 

Max. wire size (litz wire) 

4mm² Power 

terminals 

Wire size AWG 

AWG 20-10 

Power terminals 

Max. wire diameter 

2.8mm Power 

terminals 

Wire stripping length 

7mm / 0.28inch 

Power terminals 

Tightening torque 

1Nm / 9lb.inch 

Power terminals 

Size 

(wxhxd)

 

40x124x102mm Without 

DIN-rail 

Weight 

500g / 1.1b 

 

 
 

Functional Diagram 

Output

Overvoltage

Protection

AS-i +

Output

Filter

AS-i-ok

(green)

Power

Converter

Shield

AS-i

Decoupling

Unit

AS-i +

AS-i -

AS-i -

Reverse

Polarity

Protection

&

Inrush

Limiter

Chassis
Ground

+

-

Input

Fuse

&

Input

Filter

Temperature

Shut-down

 
 

Output Characteristic 

Output voltage

7A

Output current

15V

0V

1A

2A

3A

4A

0A

30.6V

5A

6A

 

 
 

Temperature Range 

Allowed output current

Ambient temperature

0A

-25

4A

+60 +70°C

3A

A: continuous

B: short term (max. 60s)

A

B

 

 