PISA11.CLASS2 Instruction Manual 
PISA11.CLASS2 Bedienungsanleitung 

 

 

 

Red Failure LEDs 

(see Fig. 7-B)

 

The red LEDs are failure indicators. Any time a red LED is on or blinking, the outputs have 
shutdown. 
Three reasons why the outputs have been shutdown: 
1)  The output current of one or more individual output channels was too high. 

In this case, the affected output channel LED is blinking and all others are illuminated. 

2)  The sum of the output current of all four output channels was exceeded. 
 

In this case, all red LEDs are blinking. 

3)  The outputs needed to be shutdown in order to maintain sufficient input voltage. 
 

In this case, all red LEDs are on and the green LED is blinking. 

The outputs can also be turned off by pushing the ON/OFF button on the front of the unit or by 
applying an external signal to the ON/OFF signal input. In this case, all red LEDs are on. 
Outputs which have shutdown must be turned on manually by pushing the reset button or by an 
external reset signal (ON/OFF signal input). A cycling of the input power does not reset the unit. The 
failure signals are stored until a reset is intentionally initiated. 
When LED 1 and 4 as well as the LEDs 2 and 3 are alternately blinking, an internal error has 
occurred. Try to reset the unit by pushing the reset button. If this does not help, ship the unit to the 
factory for inspection. 

 

Rote Fehler-LEDs 

(siehe Bild 7-B)

 

Die roten LEDs sind Fehleranzeigen. Wenn eine LED blinkt oder leuchtet wird signalisiert, dass 
die Ausgänge abgeschaltet haben. 
Drei Gründe, warum die Ausgänge abgeschaltet haben könnten: 
1)  Der Ausgangsstrom eines Ausgangskanals war zu hoch. Es blinkt die LED, deren Kanal die 

Abschaltung verursacht hat. 

2)  Die maximale Summenstrom aller 4 Ausgangskanäle wurde überschritten. In diesem Fall 

blinken alle vier LEDs. 

3)  Die Ausgänge haben abgeschaltet, um einen Spannungseinbruch auf der 

Versorgungsspannung zu vermeiden. In diesem Fall leuchten alle vier roten LEDs und die 
grüne LED blinkt. 

Zusätzlich sind die Ausgänge auch durch Drücken der ON/OFF-Taste oder durch eine externe 
Spannung am ON/OFF-Signaleingang abschaltbar. In diesem Fall sind alle vier roten LEDs an. 
Abgeschaltete Ausgänge können nur manuell durch Drücken der Reset-Taste oder durch eine 
externe Spannung am ON/OFF-Signaleingang wieder eingeschaltet werden. Ein Aus- und 
Einschalten der Versorgungsspannung reicht hierzu nicht aus. Die Fehlerzustände werden 
gespeichert bis ein beabsichtigtes Rücksetzen erfolgt. 
Wenn die LED 1 und 4 sowie die LED 2 und 3 abwechselnd blinken, liegt ein interner Fehler vor. 
Falls das Gerät sich nicht mit der Reset Taste zurücksetzen lässt, muss das Gerät zur Inspektion 
ins Werk eingesendet werden. 

Reset and ON/OFF Button 

(see Fig. 7-C)

 

This is a pushbutton which can be used for two purposes: 
1)  In a failure mode (outputs have shutdown), the outputs can be turned on again by pushing and 

holding the reset button for more than 1 second. 

2)  In normal mode (outputs have not shutdown), a short (> 50ms) push will turn all outputs ON or 

OFF. 

The unit will be shipped (factory setting) with the outputs turned-on. The ON/OFF function has no 
safety feature included. 

 

“Reset”- und “ON/OFF”-Taste 

(siehe Bild 7-C)

 

Diese Taste hat zwei Funktionen: 
1)  Im Fehlermodus (Ausgänge haben abgeschaltet) können die Ausgänge mittels dieser Taste 

wieder eingeschaltet werden, wenn diese länger als 1 Sekunde gedrückt wird. 

2)  Im Normalbetrieb (Ausgänge sind nicht abgeschaltet) bewirkt ein kurzes (>50ms) Drücken  

ein abwechselndes Ein- und Ausschalten aller Ausgänge. 

Im Anlieferzustand sind die Ausgänge eingeschaltet. Die „ON/OFF“ Funktion beinhaltet keine 
Sicherheitsfeatures. 

Synchronization of Multiple PISA Modules 

(see Fig. 7-D)

 

See description on the previous pages. 

 

Synchronisation mehrerer PISA Module 

(siehe Bild 7-D)

 

Siehe Beschreibung im vorderen Teil des Dokumentes. 

Output-OK Relay Contact 

(see Fig. 7-E)

 

This relay contact is closed when the input voltage is sufficient and the outputs are not shutdown. 

Contact closes

 when the input voltage rises above 21Vdc typically and all output channels are on. 

Contact ratings

: max. 30Vdc 1A, 30Vac 0.5A, resistive load, min. current 1mA 

 

„Output-OK“-Relais-Kontakt 

(siehe Bild 7-E)

 

Dieses Signal meldet einen Zustand, bei dem eine ausreichende Eingangsspannung vorhanden 
ist und bei dem kein Ausgang abgeschaltet hat. 

Kontakt schließt

, wenn der Eingang typisch 21V übersteigt und alle Ausgangskanäle EIN sind. 

Kontakt-Belastbarkeit:

 max. 30Vdc 1A, 30Vac 0.5A, (R-Last), min. Strom 1mA 

ON/OFF (Inhibit) and Reset Input 

(see Fig. 7-F)

 

This input signal is galvanically isolated with an integrated optocoupler and works in the same 
manner as the reset and ON/OFF button. 
In a failure mode (outputs have shutdown), the outputs can be turned on again by applying a voltage 
for more than 1 second. 
In normal mode (outputs have not shutdown), a short (> 50ms) voltage pulse will turn all outputs ON 
or OFF. The ON/OFF function has no safety feature included. 
Signal voltage for activation:  min. 10V, max. 30V. Required signal current: < 6mA. 

 

„Inhibit”- und Reset-Eingang 

(siehe Bild 7-F)

 

Dieser Signaleingang ist mittels eines eingebauten Optokopplers galvanisch vom Leistungskreis 
getrennt und funktioniert in gleicher Weise wie die „Reset“- und „ON/OFF“-Taste. 
Im Fehlermodus (Ausgänge haben abgeschaltet) können die Ausgänge durch Anlegen einer 
Spannung für länger als 1 Sekunde wieder eingeschaltet werden. 
Im Normalbetrieb (Ausgänge sind nicht abgeschaltet) bewirkt ein kurzes (>50ms) Anlegen einer 
Spannung ein abwechselndes Ein- und Ausschalten aller Ausgänge. Die „ON/OFF“ Funktion 
beinhaltet keine Sicherheitsfeatures. 
Signalspannung zum Aktivieren: min. 10V, max. 30V. Erforderlicher Signalstrom: < 6mA 

Green Input Status LED 

(see Fig. 7-G)

 

This LED monitors the input voltage. The green LED is illuminated if the input voltage is higher than 
21Vdc. The green LED will blink when the input protection circuit (Safeguard) is activated in order to 
protect the supply voltage from dropping below 21V or when the outputs have already been 
shutdown due to a low input voltage. 
Once the outputs have shutdown, a reset procedure similar to the one for the red LEDs is required. 
A reset is not necessary when the green LED is blinking and the outputs have not been shutdown. 
In this case the blinking LED will turn solid once the input voltage is sufficient again.  

 

Grüne Status LED für den Eingang 

(siehe Bild 7-G)

 

Diese LED gibt Aufschluss über die Eingangsspannung. Die grüne LED ist an, wenn die 
Eingangsspannung größer als 21V ist. Die grüne LED blinkt, wenn die Eingangsschutzschaltung 
(Schutzschild) aktiviert ist, um ein Absinken der Versorgungsspannung unterhalb 21V zu 
vermeiden oder wenn die Ausgänge bereits wegen einer zu kleinen Versorgungsspannung 
abgeschaltet haben. 
Haben die Ausgänge abgeschaltet, ist eine Rücksetzprozedur wie bei den roten LEDs 
erforderlich. Ein Rücksetzen ist jedoch nicht erforderlich, solange die grüne LED nur blinkt und 
die Ausgänge noch nicht abgeschaltet haben. Nach Beseitigung des Fehlers ist die grüne LED 
automatisch wieder an. 

 
 
 
 
 
 
 

Fig. 7 / Bild 7

 

User elements / Bedienelemente 

Fig. 8 / Bild 8

 

Dimensions (mm) / Abmessungen (mm) 

 

 

 

PU-399.010.08-10C 

 