background image

EN

PISA-B-812-B4 Installation Manual

Product Description

The PISA-B-812-B4 is a DIN-rail mountable eight channel protection module with integrated electronic
fuses for 24V systems.

Intended Use

This device is designed for installation in an enclosure and is intended for commercial use, such as in
industrial control, process control, monitoring and measurement equipment or the like.

Do not use this device in equipment, where malfunctioning may cause severe personal injury or
threaten human life without additional appropriate safety devices, that are suited for the end-
application.

If this device is used in a manner outside of its specification, the protection provided by the device may
be impaired.

Installation Instructions

Install the device in an enclosure providing protection against electrical, mechanical and fire hazards.

Install the device onto a DIN-rail according to EN 60715 with the input terminals on top of the unit.

Up to eight devices can be connected via two bus bars, where only the first device is connected to the
power supply. The bus bars must be long enough to make a connection to all contacts of the devices.

Use an appropriately sized 24V power supply, which can deliver the peak current required to trip the
load channels. If peak currents are too low, the supply voltage for the protection module can no longer
be maintained, which results in a malfunctioning of the protection module.

Make sure that the wiring is correct by following all local and national codes. Use appropriate copper
cables that are designed for a minimum operating temperature of 60°C for ambient temperatures up to
+45°C, 75°C for ambient temperatures up to +60°C and 90°C for ambient temperatures up to +70°C.
Ensure that all strands of a stranded wire enter the terminal connection.

The device is designed for pollution degree 2 areas in controlled environments. No condensation or
frost is allowed.

The enclosure of the device provides a degree of ingress protection of IP20. The housing does not
provide protection against spilled liquids.

The isolation of the devices is designed to withstand impulse voltages up to 1.5kV according to IEC
60664-1.

The input can be powered from a regulated power supply or a similar DC source.

The input must be powered from a PELV or SELV source or an “Isolated Secondary Circuit” in order to
maintain a SELV or PELV output.

Check for correct input polarity. The device will not operate when the voltage is reversed.

A disconnecting means shall be provided for the input of the device.

The device is designed as “Class of Protection III” equipment according to IEC 61140.

The device is designed for convection cooling and does not require an external fan. Do not obstruct
airflow and do not cover ventilation grid!

Keep the following minimum installation clearances: 40mm on top, 20mm on the bottom, 5mm left and
right side. Increase the 5mm to 15mm in case the adjacent device is a heat source. Between multiple
PISA-B modules, no clearance is needed.

The device is designed for altitudes up to 5000m (16 400ft).

The maximum surrounding air temperature is +70°C (+158°F). The operational temperature is the
same as the ambient or surrounding air temperature and is defined 2cm below the device.

The device is designed to operate in areas between 5% and 95% relative humidity.

Functional Description

The output can supply any kind of loads, including inductive and capacitive loads. The maximum size
of capacitive loads is specified in the “Technical Data” table. Larger load capacitors might result in an
unintended turn-off of the channel.

Do not load the individual channels with higher average currents depending on the ambient
temperature, as specified in the derating table of this document.

Do not apply return voltages from the load to the output terminals higher than 30V.

Do not parallel outputs for higher output currents.

Do not connect outputs in a series connection for higher output voltages.

Do not connect batteries for charging purposes to the output of the device.

Output channels can be switched on and off separately by pushing the corresponding control button
for longer than 50ms. A switched off channel is displayed with the uppermost red LED of the LED bar
graph.

If the sum output currents is larger than 40A the unit turns off the output channels one after another
until the sum current is below 40A.

The tripping current can be set individually for all channels.

The tripping characteristic can be set as a common parameter for all channels.

Tripping currents and characteristic setting can be protected against changes with a PIN code. To lock
the settings push the SET and channel control button 1 until the unit shows a moving text “PIN TO
LOCK”. Enter a 4-digit PIN by pushing any combination of channel control buttons 1-8. Push the SET
button to save the PIN, the unit shows a moving text “LOCKED”.
To unlock settings push the SET and channel control button 1, the unit shows a moving text “PIN TO
UNLOCK” and enter the 4-digit PIN you selected and confirm it by pushing the SET button.

The device is equipped with a “Digital Coded Alarm Signal” output (pins 13 and 14), which provides
information about individual channel tripping. The signal is an opto-coupler-type output which is low
ohmic for start bit and for tripped channels. The maximal signal current between pins 13 and 14 is
10mA and the maximal voltage is 35V.
The signal sequence starts with 200ms start bit followed by a 100ms gap and 100ms signal related to
CH1 etc. The whole sequence is periodically repeated every 1900ms.

Technical Data

All values are typical figures specified at 24Vdc input voltage, 8x 5A output
currents, 25°C ambient temperature and after a 5 minutes run-in time
unless otherwise noted.

Input voltage

DC 24V

-20%/+25%

Required input voltage for
turning-on of outputs

19.6Vdc

Input current

40A

Internal consumption

35mA

Nominal output current

Adjustable

1/2/3/4/6/8/10/12A For CH1 and CH2
1/2/3/4/6/8/10A

For CH3-CH8

Sum current all channels

40A

Below +60°C ambient

30A

At +70°C ambient

Derate linearly b60°C and +70°C

Current limitation
CH1-CH2

200%

For 1A setting

150%

For 2 - 8A settings

130%

For 10 - 12A settings

CH3-CH8

50A

Tripping characteristics

Slow or fast

Selectable

Tripping delay
CH1-CH2

2ms – 2s

At short circuit

CH3-CH8

<10ms

At short circuit

CH1-CH8

1.1s

For slow tripping setting
at 1.5x nominal current

CH1-CH8

0.22s

For fast tripping setting
at 1.5x nominal current

Max load capacitance capability
CH1-CH2

100mF

Per channel

CH3-CH8

20mF

Per channel

Voltage drop per channel
CH1-CH2

125mV

For 10A load

CH3-CH8

165mV

For 10A load

Standby losses

1W

Power losses

10.8W

At 8x 5A load current

Temperature range

-25°C to 70°C

Max. wire size (litz wire)

16mm²

For input terminals

Max. wire size with ferrules

10mm²

For input terminals

Wire size AWG

AWG 20-4

For input terminals

Maximum wire diameter

6.1mm

For input terminals

Wire stripping length

19mm/ 0.75inch 

For input terminals

Max. wire size (litz wire)

2.5mm²

For output terminals

Max. wire size with ferrules

1.5mm²

For output terminals

Wire size AWG

AWG 24-12

For output terminals

Maximum wire diameter

2.3mm

For output terminals

Wire stripping length

10mm / 0.4inch

For output terminals

Max. wire size (litz wire)

2.5mm²

For signal terminals

Max. wire size with ferrules

1.5mm²

For signal terminals

Wire size AWG

AWG 24-12

For signal terminals

Maximum wire diameter

2.3mm

For signal terminals

Wire stripping length

10mm / 0.4inch

For signal terminals

Size

(w x h x d)

52x124x130mm 

Without DIN-rail

Weight

370g/0.82lb

Functional Diagram

+

-

Ch 1

Channel Switch,

Current Sense

+

-

Ch 2

Channel Switch,

Current Sense

+

-

Ch 8

Channel Switch,

Current Sense

Master Switch

(Fail-safe)

Controller

LED Matrix

Display

+

-

Input

13

14

Digital

Coded

Alarm

Signal

11

12

Reset

Input

Control

Button Ch 1

Control

Button Ch 2

Control

Button Ch 8

+

SET Button

+

-

Power Busbar

Digital Coded Alarm Signal – Signal Sequence

CH1

Alarm

CH2

Alarm

CH6

Alarm

Start

Bit

Start

Bit

100ms / DIV

1 Sequence (1900ms)

Example: CH1, CH2 and CH6 have tripped

Reviews: