MLY02.100
MiniLine
MLY-Series
DC12-48V
(120V),
10A,
D
UAL
R
EDUNDANCY
M
ODULE
R
EDUNDANCY
M
ODULE
Cost Effective Solution to Build Redundant Systems
Dual Input with Single Output
Two Diodes (Common Cathode)
DC12-48V (120Vdc) ±25% Wide-range Input
Full Power Between -40°C and +60°C
Compact Design, Width only 45mm
Quick-connect Spring-clamp Terminals
Easy Wiring:
Distribution Terminal for Negative Pole Included
3 Year Warranty
1/16
G
ENERAL
D
ESCRIPTION
The MLY02.100 is a simple is a redundancy module,
which can be used to build 1+1 and N+1 redundant
systems. It is equipped with two input channels, which
can be connected to power supplies with up to 5A
output current and one output, which can carry
nominal currents up to 10A. The module is suitable for
power supplies with constant current overload behavior
as well as any kind of “Hiccup” overload behavior.
Unique quick-connect spring-clamp terminals allow a
safe and fast installation and a large international
approval package for a variety of applications makes
this unit suitable for nearly every situation.
S
HORT
-
FORM
D
ATA
Input voltage
DC 12-48V
±25%
DC 12-120V
±25%
w/o restrictions
with restrictions
Input voltage
range
9-60Vdc
9-150Vdc
w/o restrictions
with restrictions
Input current
2x 0-5A
continuous
2x 0-8A
for 5 seconds
Output current
0-10A
continuous
10-16A
for 5 seconds
<16A
at cont. overload/
short circuit
Input to output
voltage drop
typ. 0.8V
typ. 0.9V
typ. 0.9V
input: 2x2.5A
input: 1x5A
input: 2x5A
Power losses
typ. 0W
at no load
typ. 4.0W
input: 2x2.5A
typ. 4.5W
input: 1x5A
typ. 9.0W
input: 2x5A
Temperature range -40°C to +70°C
operational,
Derating
0.25A/°C
+60 to +70°C
Dimensions
45x75x91mm
WxHxD
O
RDER
N
UMBERS
Redundancy
MLY02.100
12-48V
(120V)
Module
Standard unit
Accessory --
M
ARKINGS
IND. CONT. EQ.
UL 508
UL 60950-1
Class I Div 2
IECEx
ATEX
II 3G Ex nA IIC T4 Gc
Marine
EMC, LVD
Apr. 2014 / Rev. 1.3 DS-MLY02.100-EN
All parameters are specified at 24V, 10A output current, 25°C ambient and after a 5 minutes run-in time unless otherwise noted