ML60.241
MiniLine-2
24V,
2.5A,
S
INGLE
P
HASE
I
NPUT
21.
A
CCESSORY
21.1.
ZM3.WALL
–
W
ALL
M
OUNT
B
RACKET
DIN-Rail bracket for wall or panel mount:
The picture of the power supply is for representation only
Hole diameter: 4.2mm
21.2.
MLY10.241
-
R
EDUNDANCY
M
ODULE
MLY10
IN 1
+
-
+
-
L
N
I
I
ML60.241
L N
Output
Input
+ +
- -
ML60.241
L N
Output
Input
+ +
- -
Output
Load
+
- -
+
-
IN 2
Voltage
Monitor
The MLY10.241 is a dual redundancy module,
which has two diodes with a common cathode
included. It can be used for various purposes.
The most popular application is to configure
highly reliable and true redundant power
supply systems. Another interesting
application is the separation of sensitive load
from non-sensitive loads. This avoids the
distortion of the power quality for the
sensitive loads which can ca
s
use controller
failures.
ODULE
21.3.
UF20.241 - B
UFFER
M
This buffer unit is a supplementary device for DC 24V power supplies. It delivers power to bridge typical mains failures
or extends the hold-up time after turn-off of the AC power. In times when the
power supply provides sufficient voltages, the buffer module stores energy in
integrated electrolytic capacitors. In case of mains voltage fault, this energy is
released again in a regulated process. One buffer module can deliver 20A which can
also be used to support peak current demands.
The buffer unit does not require any control wiring. It can be added in parallel to
the load circuit at any given point. Buffer
units can be added in parallel to increase
the output ampacity or the hold-up time.
DC
Buffer
Unit(s)
Power
Supply
Load
AC
+
-
Nov. 2015 / Rev. 1.4 DS-ML60.241-EN
All parameters are specified at 24V, 2.5A, 230Vac 50Hz input, 25°C ambient and after a 5 minutes run-in time unless otherwise noted.
www.pulspower.com Phone +49 89 9278 0 Germany
17/23