ML60.241
MiniLine-2
24V,
2.5A,
S
INGLE
P
HASE
I
NPUT
P
OWER
S
UPPLY
100-240V Wide Range Input
NEC Class 2 Compliant
Adjustable Output Voltage
Efficiency up to 89.7%
Low No-load Losses and Excellent Partial-load Efficiency
Compact Design, Width only 45mm
Full Power between -10°C and +60°C
Large International Approval Package
3 Year Warranty
1/23
G
ENERAL
D
ESCRIPTION
A compact size, light weight, simple mounting onto the
DIN-rail and the utilization of only quality components
are what makes the MiniLine power supplies so easy to
use and install within seconds.
A rugged electrical and mechanical design as well as a
high immunity against electrical disturbances on the
mains provides reliable output power. This offers
superior protection for equipment which is connected
to the public mains network or is exposed to a critical
industrial environment.
The MiniLine series offers output voltages from 5 to
56Vdc and a power rating from 15W to 120W.
The supplementary MiniLine decoupling diode module
MLY10.241 allows building of redundant systems or to
protect against back-feeding voltages.
S
HORT
-
FORM
D
ATA
Output voltage
DC 24V
Adjustment range
24 - 28V
Output current
2.5A at 24V
2.1A at 28V
Output power
60W
Output ripple
< 50mVpp
20Hz to 20MHz
Input voltage
AC 100-240V
-15% / +10%
Mains frequency
50-60Hz
±6%
AC Input current
0.98 / 0.58A
at 120 / 230Vac
Power factor
0.58 / 0.5
at 120 / 230Vac
AC Inrush current
typ. 16 / 32A
peak value at 120
/ 230Vac 40°C
and cold start
DC Input
88-375Vdc
below 110Vdc
derating required
Efficiency
87.8 / 89.7%
at 120 / 230Vac
Losses
8.3 / 6.7W
at 120 / 230Vac
Temperature range -10°C to +70°C
operational
Derating
1.5W/°C
+60 to +70°C
Hold-up time
typ. 24 / 107ms
at 120 / 230Vac
Dimensions 45x75x91mm
WxHxD
Weight
250g / 0.55lb
O
RDER
N
UMBERS
Power Supply
ML60.241
24-28V Standard unit
Accessory MLY10.241
Redundancy
Module
UF20.241
Buffer
Module
ZM3.WALL
Wall
mount
bracket
M
ARKINGS
Ind. Cont. Eq. UL 508
UL 60950-1
Marine
Class I Div 2
NEC
Class 2
EMC, LVD
Nov. 2015 / Rev. 1.4 DS-ML60.241-EN
All parameters are specified at 24V, 2.5A, 230Vac 50Hz input, 25°C ambient and after a 5 minutes run-in time unless otherwise noted.
www.pulspower.com Phone +49 89 9278 0 Germany