ML50.100, ML50.109
MiniLine
24V, 2.1A, S
INGLE
P
HASE
I
NPUT
Mar. 2007 / Rev. 1.0 DS-ML50.100-EN
All parameters are specified at 24V, 2.1A, 230Vac, 25°C ambient and after a 5 minutes run-in time unless otherwise noted.
www.pulspower.com Phone +49 89 9278 0 Germany
14/20
24. P
HYSICAL
D
IMENSIONS AND
W
EIGHT
Weight
240g / 0.53lb
DIN-Rail
Use 35mm DIN-rails according to EN 60715 or EN 50022 with a height of 7.5 or 15mm.
The DIN-rail height must be added to the depth (91mm) to calculate the total required
installation depth.
Electronic files with mechanical data can be downloaded at www.pulspower.com
Fig. 24-1
Front view
Fig. 24-2
Side view
25. I
NSTALLATION AND
O
PERATION
I
NSTRUCTIONS
Mounting:
Output terminal must be located on top and input terminal on the bottom. For other orientations see chapter 27.12.
An appropriate electrical and fire end-product enclosure should be considered in the end use application.
Cooling:
Convection cooled, no forced cooling required. Do not cover ventilation grill (e.g. cable conduits) by more than 30%!
Installation clearances:
25mm on top and bottom.
Risk of electrical shock, fire, personal injury or death!
Do not use the unit without proper earth connection (Protective Earth).
Turn power off before working on the power supply. Protect against inadvertent re-powering.
Make sure the wiring is correct by following all local and national codes.
Do not open, modify or repair the unit.
Use caution to prevent any foreign objects from entering into the housing.
Do not use in wet locations or in areas where moisture or condensation can be expected.
Service parts:
The unit does not contain any service parts. The tripping of an internal fuse is caused by an internal fault. If damage
or malfunctioning should occur during operation, immediately turn power off and send unit to the factory for
inspection!