350g / 0.77lb
DIN-Rail
Use 35mm DIN-rails according to EN 60715 or EN 50022 with a height of 7.5 or 15mm.
The DIN-rail height must be added to the depth (117mm) to calculate the total required installation depth.
Electronic files with mechanical data can be downloaded at www.pulspower.com
Fig. 20-1
Front view
Fig. 20-2
Side view
21. I
NSTALLATION AND
O
PERATION
I
NSTRUCTIONS
Mounting Orientation:
Input terminal must be located on top and output terminal on the bottom. For other orientations see section 0
Cooling:
Convection cooled, no forced cooling required. Do not cover ventilation grid (e.g. cable conduits) by more than 30%!
Installation clearances:
40mm on top, 20mm on the bottom, 5mm on the left and right side are recommended when loaded permanently
with full power. In case the adjacent device is a heat source, 15mm clearance is recommended.
Risk of electrical shock, fire, personal injury or death!
Turn power off before working on the module. Protect against inadvertent re-powering.
Make sure the wiring is correct by following all local and national codes.
Do not open, modify or repair the unit.
Use caution to prevent any foreign objects from entering into the housing.
Do not use in wet locations or in areas where moisture or condensation can be expected.
Service parts:
The unit does not contain any serviceable parts.