All parameters are specified at 24V, 20A output current, 25°C ambient and after a 5 minutes run-in time unless otherwise noted.
www.pulspower.com Phone +49 89 9278 0 Germany
13/17
23. A
PPLICATION
N
OTES
23.1. R
ECOMMENDATIONS FOR
R
EDUNDANCY
Recommendations for the configuration of redundant power systems:
•
Use separate input fuse for each power supply.
•
Use Three-phase power supplies to gain functional safety if one phase fails.
•
When Single-phase power supplies are utilized connect them to different phases or mains circuits.
•
Use both inputs in parallel for currents above 10A.
23.2. 1+1 R
EDUNDANCY UP TO
10A
1+1 Redundancy up to 10A requires two 10A power supplies and one YRM2.DIODE redundancy module.
Fig. 23-1
Wiring diagram, 1+1 Redundancy, 10A output current
Failure
Monitor
10A
Load
optional
I
I
L
N
PE
L N PE
+ +
- -
Power Supply
24V, 10A
YRM2.DIODE
+
-
OUT
+
-
IN 1
+
-
IN 2
IN 1 IN 2
L N PE
Power Supply
+ +
- -
24V, 10A