UC10.241, UC10.242
UC-Series
24V,
15A,
CAPACITOR-BASED
DC-UPS
5.
C
HARGING
During charging, the DC-UPS consumes additional current from the input. See chapter “Input”.
When charging is completed, the “Ready LED” stops flashing and is on solid and the “Ready relay contact” closes.
UC10.241 UC10.242
Charging time
initial
charging
*)
typ.
16 minutes
32 minutes
when capacitor is completely discharged
Charging time
recharging
**)
typ.
1 minute 50s
1 minute 50s
after discharging with 10A for 10s
typ.
3
minutes
50s
7 minutes 40s
after discharging with 10A until buffering
stops
typ.
4
minutes
40s
9 minutes 40s
after discharging with 5A until buffering
stops
typ.
5
minutes
40s
11 minutes
15s
after discharging with 1A until buffering
stops
Allowed number of charging/
discharging cycles
no limitation
no limitation
*)
Initial charging means that no input voltage was applied for several hours or longer and the capacitor is completely discharged by the
internal electronics.
**) Recharging means that the electronics inside the DC-UPS has not completely discharged the capacitor. The values in the table apply when
the input voltage is applied immediately after buffering has stopped.
Note:
At the end of the charging process the active balancing circuit reduces the charging current periodically, which can be
seen as current oscillations on the input current.
May 2016 / Rev. 2.2 DS-UC10.241-EN
All parameters are specified at 24V, 10A output current, 25°C ambient and after a 5 minutes run-in time unless otherwise noted.
www.pulspower.com Phone +49 89 9278 0 Germany
7/27