Puls Dimension CP Series Manual Download Page 26

 

 

CP20.245-R2 

 

 

 

 

CP-Series 

24V,

 

20A,

 

S

INGLE 

P

HASE 

I

NPUT

 

 

 

Aug. 2022 / Rev 1.1 DS-CP20.245-R2 EN  

All parameters are typ. values specified at 24V, 20A, 230Vac, 25°C ambient and after a 5 minutes run-in time unless otherwise noted. 

www.pulspower.com   Phone +49 89 9278 0    Germany 

26/28 

24.6.

 

S

ERIES 

O

PERATION

  

Power supplies of the same type can be connected in series for higher output voltages. It is possible to connect as 
many units in series as needed, providing the sum of the output voltage does not exceed 150Vdc. Voltages with a 
potential above 60Vdc are not SELV anymore and can be dangerous. Such 
voltages must be installed with a protection against touching.  
Avoid return voltage (e.g. from a decelerating motor or battery) which is 
applied to the output terminals.  
Keep an installation clearance of 15mm (left / right) between two power 
supplies and avoid installing the power supplies on top of each other. Do 

not use power supplies in series in mounting orientations other than the 
standard mounting orientation (input terminals on bottom of the unit). 
Pay attention that leakage current, EMI, inrush current, harmonics will 
increase when using multiple power supplies. 
 

24.7.

 

P

ARALLEL 

U

SE TO 

I

NCREASE 

O

UTPUT 

P

OWER

 

Power supplies can be paralleled to increase the output power. For 

redundancy applications one extra power supply is always needed for 
sufficient output current in case one unit fails. 
The unit is permanently set to “parallel use” mode in order to achieve 
load sharing between power supplies connected in parallel. The “Parallel 

use” mode regulates the output voltage in such a manner that the voltage 
at no load is approx. 4% higher than at nominal load. See also chapter 6. 
Energize all units at the same time to avoid the overload Hiccup

PLUS

 mode. 

It also might be necessary to cycle the input power (turn-off for at least 

five seconds), if the output was in Hiccup

PLUS

 mode due to overload or 

short circuits and the required output current is higher than the current of one unit. 
Keep an installation clearance of 15mm (left / right) between two power supplies and avoid installing the power 
supplies on top of each other.  
Do not use power supplies in parallel in mounting orientations other than the standard mounting orientation (input 
terminals on bottom of the unit) or in any other condition where a derating of the output current is required (e.g. 
altitude). 
Pay attention that leakage current, EMI, inrush current, harmonics will increase when using multiple power supplies. 
Do not load paralleled power supplies with higher currents as shown in the following diagrams: 
 

 

Fig. 24-5

   Output current vs. ambient temp. for 

two paralleled units 

 

Fig. 24-6

   Output current vs. ambient temp. 

for three paralleled units 

 

Allowed output current for two paralleled units

0

30

40

50

60

70°C

8A

16A

24A

32A

40A

48A

B

A

Ambient Temperature

A... continuous
B... short term (max. 5s)

36.6

28A

 

 

Allowed output current for three paralleled units

0

30

40

50

60

70°C

12A

24A

36A

48A

60A

72A

B

A

Ambient Temperature

A... continuous
B... short term (max. 5s)

36.6

42A

 

 

Unit A

Unit B

-

+

-

+

Load

+

-

Input

Output

Input

Output

Unit A

Input

Output

Unit B

-

+

-

+

Load

+

-

Input

Output

Summary of Contents for Dimension CP Series

Page 1: ...systems and plug connector terminals to allow device replacement while the application keeps running The CP20 245 R2 covers an extreme wide temperature range from 40 C up to 60 C providing full outpu...

Page 2: ...ed Enclosure 28 24 12 Mounting Orientations 29 The information given in this document is correct to the best of our knowledge and experience at the time of publication If not expressly agreed otherwis...

Page 3: ...ons require a reduction in output current Make sure that the wiring is correct by following all local and national codes Use appropriate copper cables that are designed for a minimum operating tempera...

Page 4: ...me unless otherwise noted www pulspower com Phone 49 89 9278 0 Germany 4 28 The maximum surrounding air temperature is 70 C The operational temperature is the same as the ambient or surrounding air te...

Page 5: ...1 65 1 63 1 63 At 20A Start up delay typ 450ms 420ms 440ms See Fig 3 2 Rise time typ 145ms 145ms 145ms At 20A const current load 0mF load capacitance see Fig 3 2 typ 160ms 160ms 160ms At 20A const cur...

Page 6: ...r Supply AC DC Battery N a Use a battery or a similar DC source A supply from the intermediate DC bus of a frequency converter is not recommended and can cause a malfunction or damage the unit b Conne...

Page 7: ...see Fig 6 3 The output voltage stays above 20V See chapter 24 1 for more peak current measurements Overload behaviour Continuous current Output voltage 13Vdc see Fig 6 1 HiccupPLUS mode Output voltage...

Page 8: ...c behavior 12ms 0 0 4 8 12 28V 16 20 24 70A 30 10 40 50 20 60 Output Current 7 HOLD UP TIME AC 100V AC 120V AC 230V Hold up Time typ 65ms 65ms 65ms At 10A see Fig 7 1 min 54ms 54ms 54ms At 10A see Fig...

Page 9: ...power supply in front of the decoupling device see also chapter 11 Contact closes As soon as the output voltage reaches typ 22Vdc Contact opens As soon as the output voltage dips below 22Vdc Short di...

Page 10: ...n assumption for a typical application where the power supply is loaded with 25 of the nominal load for 25 of the time 50 of the nominal load for another 25 of the time 75 of the nominal load for anot...

Page 11: ...ectrolytic capacitors Lifetime expectancy is specified in operational hours and is calculated according to the capacitor s manufacturer specification The manufacturer of the electrolytic capacitors on...

Page 12: ...mm2 max 6mm2 max 1 5mm2 American Wire Gauge AWG 20 12 AWG 24 10 AWG 26 14 Max wire diameter 2 4mm including ferrules 3 2mm including ferrules 1 8mm including ferrules Recommended tightening torque max...

Page 13: ...system is running Load I I L N PE 1a L N PE CP20 241 R2 73 Power Supply DC OK DC OK Output 24V 20A Input L N PE CP20 241 R2 73 Power Supply DC OK DC OK Output 24V 20A Input 1b 2a 3a 3b 2b Instructions...

Page 14: ...8 0 Germany 14 28 14 FRONT SIDE AND USER ELEMENTS Fig 14 1 Front side A Input Terminals plug connector N L Line input PE Protective Earth input B Output Terminals plug connector Positive output Negati...

Page 15: ...Criterion C Criterion A Criterion A Criterion A Criterion A Voltage interruptions EN 61000 4 11 0 of 200Vac 0V 5000ms Criterion C Voltage sags SEMI F47 0706 Dips on the input voltage according to SEMI...

Page 16: ...heric pressures from 80 47kPa Degree of pollution 2 acc IEC 61010 2 201 not conductive Vibration sinusoidal3 2 17 8Hz 1 6mm 17 8 500Hz 2g 2 hours axis IEC 60068 2 6 Shock3 30g 6ms 20g 11ms 3 bumps dir...

Page 17: ...y critical situations e g customer does not care about de rating requirements ambient temperature too high obstructs the airflow or install the unit in unsuitable mounting orientation There is no corr...

Page 18: ...ng set the cut off current settings to the value in the table below Fig 19 1 Dielectric strength A B C D A D C B B N L Input DC ok Earth PE Output Type test 60s 2500Vac 3000Vac 1000Vac 500Vac Factory...

Page 19: ...ble for US and Canada E File E198865 ATEX Agency Certificate Bureau Veritas EN 60079 0 Explosive atmospheres General requirements EN 60079 7 EN 60079 15 Equipment protection by type of protection e an...

Page 20: ...according to VDMA 24364 C1 L W for solvents and water based paints 21 REGULATORY PRODUCT COMPLIANCE CE EU Declaration of Conformity Trade conformity assessment for Europe The CE mark indicates conform...

Page 21: ...GHT Width 48mm Height 124mm without plug connectors Depth 127mm without plug connector The DIN rail depth must be added to the unit depth to calculate the total required installation depth DIN Rail Us...

Page 22: ...23 ACCESSORIES 23 1 ZM10 WALL WALL PANEL MOUNT BRACKET This bracket is used to mount the devices on a wall panel without utilizing the DIN Rail The bracket can be mounted without detaching the DIN ra...

Page 23: ...to trip fuses on faulty output branches or to start peak current demanding loads Solenoids contactors and pneumatic modules often have a steady state coil and a pick up coil The inrush current demand...

Page 24: ...haracteristic a setting to 24 0V results to an output voltage of 23 8V 0 2 at 24A and 25 0V 0 2 at no load See Fig 24 3 Output current min 24A At 45 C min 20A At 60 C min 15A At 70 C Reduce output cur...

Page 25: ...AC supply systems and may also be used on 24V branches MCB s are designed to protect wires and circuits If the ampere value and the characteristics of the MCB are adapted to the wire size that is used...

Page 26: ...load sharing between power supplies connected in parallel The Parallel use mode regulates the output voltage in such a manner that the voltage at no load is approx 4 higher than at nominal load See al...

Page 27: ...individual power supply units Therefore use the built in DC OK relay contact of the power supply Fig 24 7 Wiring diagram 1 1 Redundancy for 20A output current 24V 20A Load L N PE Failure Monitor I I L...

Page 28: ...phase to phase connection is allowed as long as the supplying voltage is below 240V 10 24 11 USE IN A TIGHTLY SEALED ENCLOSURE When the power supply is installed in a tightly sealed enclosure the temp...

Page 29: ...nded output current Curve A2 Max allowed output current results in approximately half the lifetime expectancy of A1 Fig 24 9 Mounting Orientation A Standard orientation Power Supply OUTPUT INPUT Outpu...

Reviews: