CP20.245-R2
CP-Series
24V,
20A,
S
INGLE
P
HASE
I
NPUT
Aug. 2022 / Rev 1.1 DS-CP20.245-R2 EN
All parameters are typ. values specified at 24V, 20A, 230Vac, 25°C ambient and after a 5 minutes run-in time unless otherwise noted.
www.pulspower.com Phone +49 89 9278 0 Germany
12/28
12.
T
ERMINALS AND
W
IRING
The terminals are IP20 Finger safe constructed and suitable for field- and factory wiring.
Input
Output
DC-OK-Signal
Type
plug connector with
screw termination
plug connector with
screw termination
plug connector with
screw termination
Solid wire
max. 4mm
2
max. 6mm
2
max. 1.5mm
2
Stranded wire
max. 2.5mm
2
max. 6mm
2
max. 1.5mm
2
American Wire Gauge
AWG 20-12
AWG 24-10
AWG 26-14
Max. wire diameter
2.4mm
(including ferrules)
3.2mm
(including ferrules)
1.8mm
(including ferrules)
Recommended tightening torque
max. 0.5Nm
max. 0.6Nm
max. 0.8Nm
Wire stripping length
7mm
12mm
6mm
Screwdriver
3.5mm slotted or cross-
head No 2
3.5mm slotted or cross-
head No 2
3.5mm slotted
Instructions:
a) Use appropriate copper cables that are designed for minimum operating temperatures of:
60°C for ambient up to 45°C and
75°C for ambient up to 60°C minimum
90°C for ambient up to 70°C minimum.
b) Follow national installation codes and installation regulations!
c) Ensure that all strands of a stranded wire enter the terminal connection!
d) Unused terminal compartments should be securely tightened.
e) Ferrules are allowed.