TSC 1500XL
8
- Connecting the Master Node to Secondary Node panels.
•
Serial Data cable equivalent to Carol C0842A or Belden 9842 (120-ohm impedance).
CAT Ethernet cable cannot be used. No Substitutions.
•
Requires RJ-45 connector (Included per Node panel).
- Master Node connections.
Figure 5
NOTE:
Strip Serial Data cable no more than 2” from the end. Clip off any unused wires. Route
Serial Data cable away from any high voltage lines when connecting to secondary node panels.
1.
Connect the Serial Data cable to the Master PLC as shown in Figure 5. Use the chart for
correct wire assignments.
2.
Make sure Serial Data cable shielding is landed on the shield terminal at the PLC.
3.
When connecting to Secondary Nodes, use the supplied RG-45 connector.
4.
See page 9 for Pin assignments for the supplied RJ-45 connector.
TSC Cable Termination
Example.
Signal Name
Master PLC
NC
No Connection
CAN.H
OR/WH
Shield
BARE SH
CAN.L
OR
GND
GR/ WH