background image

Wiring the Discharge Air Temperature Sensor

Connect the red and white thermostat wires to the LAT Sensor
(TS2) terminals as shown below.  

Outdoor Sensor

Red

White

Zoning Panel

LAT

LAT

Leaving Air Temperature Sensor Input

Leaving Air Temperature Sensor Input

From Discharge

Temperature

Sensor (TS2)

Terminal Function

1

2

3

7

To Zoning Panel

Plenum

4

5

6

GND

PRS

OAT

LAT

OAT

LAT

+VDC

SENSOR

S

Zoning Panel

6

GND

PRS

OAT

LAT

OAT

LAT

+VDC

SENSOR

S

Installing the Outdoor Temperature Sensor

Wiring the Outdoor Temperature Sensor

The outdoor temperature sensor (TS3) should be placed in a 
shaded location and protected from rain or snow such as under 
the eves of a home.  Select a location and drill a 5/16-inch 
diameter hole to pass the sensor wires through.

Remove screw (1) and separate the base (5) and the cover (2).  
Pass a 2-wire thermostat cable through the wall, through the 
gasket (6) and through the base (5).  Secure the base (5) to the 
wall with the gasket (6) between the base and wall using the 
two mounting screws (4).  Connect the red and white 
thermostat wires to the thermistor wires (no polarity) using the 
wirenuts (3).  Push the wirenuts and wire into the cover and 
secure the cover with the screw (1). 

Connect the red and white thermostat wires to the OAS Sensor
(TS3) terminals as shown below.  

Zoning Panel

Outdoor Sensor

Red

White

Zoning Panel

OAT

OAT

Outdoor Temperature Sensor Input

Outdoor Temperature Sensor Input

From Outdoor

Temperature

Sensor (TS3)

Terminal Function

Discharge Air Temperature Sensor (Model TS2)

The optional discharge or leaving air temperature sensor (TS2) 
can be used to limit discharge air temperature in heating and 
cooling to prevent over-heating the plenum or freezing the 
indoor coil when only a small number of zones are calling.   

o

The panel is factory set for 160 F heating limit for gas heating 

o

and 140 F for compressor heating.  If the discharge 
temperature exceeds these limits, the panel will down-stage or 
turn the heating off (fan continues to operate) until the 
temperature is within limits.  In cooling the factory limit is set to 

o

45 F.  The PDMi3 can be used to digitally adjust these limits.

Installing the Discharge Air Temperature Sensor

Warning!

Drill a 3/8-inch diameter hole in the plenum or supply duct.  
Remove the screw (1) to separate the cover (2) and base (5).  
Insert the sensor tube (7) through the gasket and the drilled 
hole.  Attach the base to the plenum or duct using the two 
mounting screws (4).  Use the wire nuts (3) to connect the red 
and white thermostat wires to the two thermistor wires.  Place 
the wires into the cover and through the U-shaped tab at the 
bottom of the base.  Install the cover using the screw (1).

The discharge temperature sensor (TS2) has a 6-inch long, 
stainless steel tube that goes into the discharge airstream in 
the plenum or main supply duct. 

Be careful when drilling holes in the plenum to avoid 
puncturing the indoor coil or damaging other components.

Summary of Contents for ProR212J

Page 1: ...nfigure a zone All panels operate with gas electric systems conventional heat pumps and dual fuel heat pumps Selected using the jumper plugs on the panel See table below See table below See table belo...

Page 2: ...ir damper is open LEDs indicate zone damper position Multi color LEDs indicate equipment call status Jumper plugs for selecting type of equipment Multi color LEDs indicate zoning panel status Terminal...

Page 3: ...n below 1 3 HVAC PANEL ZONE DAMPERS 1 1 2 2 3 FAD 3 THERMOSTATS Quick View ProR321J Zoning Panel ProZone Two 8 screws Two 8 screws Panel 3 Zone Maximum VA 40VA Transformer 60VA Transformer 75VA Transf...

Page 4: ...VAC Thermostat R C Y or Y1 G Zoning Panel R C 24VAC 24VAC Common Cooling Stage1 Indoor Fan Y G Terminal Function W1 OB Stage1 Heating W1 OB Inside Day Th MODE MENU FAN SYSTEM Schedule Auto Heat Heat S...

Page 5: ...AC EQUIPMENT W2 E Y2 R R O O B W1 B W Y Y1 Wiring HVAC Equipment Gas Electric System Two Stage Heat Gas Electric System Two Stage Cool Gas Electric systems using a single 24VAC transformer are wired a...

Page 6: ...ature Sensor Input Outdoor Temperature Sensor Input From Outdoor Temperature Sensor TS3 Terminal Function Discharge Air Temperature Sensor Model TS2 The optional discharge or leaving air temperature s...

Page 7: ...nd releasing the MENU key accesses the User menu where settings and data can be viewed but not changed 9 EXT PDMi MENU MENU NEXT NEXT SAVE SAVE PDM Programming Display Module PDM Programming Display M...

Page 8: ...and cooling the fan operation the supply air temperature limits outdoor changeover temperature for dual fuel heat pumps and number of zones being used Press No to continue Press Yes to change the siz...

Page 9: ...ing control The equipment type is set by the jumper plugs and cannot be changed with PDMi3 Press Yes to continue to select additional options Press Yes to select conventional heat pump If equipment ty...

Page 10: ...ats that can be used in that zone Press Up or Down to change the number of auxiliary heating stages Press NEXT to continue Press Up or Down to change the heating temperature limit Press NEXT to contin...

Page 11: ...he bypass position of the damper when it is being used for bypass Press Next to set the bypass position of the next damper Press Up or Down to adjust the bypass position of the damper when it is being...

Page 12: ...s NEXT to continue Press Yes to enter the minutes of fresh air operation required each hour Press No to select calculating the CFM and minutes per hour Press Yes to change the Fresh Air Option Press n...

Page 13: ...pposite system service The panel normally services heating or cooling calls based on the number of calls from the zones If there are more heating calls than cooling it will service heating and vice ve...

Page 14: ...t a test stage2 heating to insure discharge temperature is correct or return to the main menu if only one stage of heating is used Press Yes to start a bypass test A test will be started based on the...

Page 15: ...Press NEXT to go to the next letter in the name Press SAVE to save the clone name Monitor HVAC Performance Y N LAT 122 Prs 0 55 BP Pos 0 NEXT Press Yes to display the leaving air temperature duct pres...

Page 16: ...una Hills CA 92653 949 916 0945 Fax 949 458 8502 www ProZone US com Limited 5 Year Warranty The 5 year warranty is limited to the repair or replacement of defective product due to parts failure or def...

Reviews: