background image

12

A damper can be used to bring outdoor air into the return to 
maintain a healthy home.  The equipment fan draws in the 
outdoor air and mixes it with the return air from the home. 
The panel attemps to fulfill the required fresh air during 
heating and cooling calls. As the end of each hour 
approaches, the panel will open the fresh air damper and 
activate the indoor fan (G) if additional fresh air minutes are 
required.  

The PDMi3 allows the installer to directly set the minutes 
per hour the fresh air damper is open or the PDMi3 can 
calculate the required CFM of fresh air based on the area 
of the home and the number of bedrooms. 

Fresh air operation is factory set to Off.  

If the contractor has calculated the CFM for fresh air and sized 
the damper to operate for a number of minutes each hour, the 
minutes can be directly entered.

The PDMi3 allows the installer to calculate the required CFM of 
fresh air based on the area of the home and the number of 
bedrooms.  The calculated CFM is the CFM required if the fresh 
air damper is continuously open and the indoor fan operating to 
draw in fresh air.  

The PDMi3 tutors the installer to set the area of the home in 
square feet and the number of bedrooms.  It then calculates and 
displays the minimum amount of outdoor air required to meet the 
requirement for the home.  This is the amount required if the 
indoor fan was running continuously.

If the fresh air intake is increased, the fresh air operation can 
occur mostly during calls to minimize dis-comfort.  The PDMi3 will 
then display the number of minutes of fresh air operation required 
each hour based on the minimum CFM and the selected CFM.

Fresh Air Control for Title24 and ASHRAE 62.2

Change or Set Fresh Air Operation

Direct Entry of Minutes per Hour of Fresh Air

PDMi3 Calculates Minutes per Hour of Fresh Air

Press Up or Down to set the area of 
the home.  Press NEXT to continue.

Press Yes to have the PDMi3 calculate 
the fresh air requirements.  Press No to 
directly set the minutes per hour of fresh 
air operation.continue.

Press Up or Down to set the 
number of minutes the fresh air 
damper and indoor fan must 
operate each hour to meet the fresh 
air requirements.  Press NEXT to 
continue.

Press Yes to enter the minutes of 
fresh air operation required each 
hour.  Press No to select calculating 
the CFM and minutes per hour.

Press Yes to change the Fresh Air 
Option.  Press no to continue to 
another option.

Press Yes to turn the Fresh Air 
Option On or No to turn it Off.

Press Up or Down to set the 
bedrooms in the home.  Press NEXT 
to continue.

The PDMi3 shows the minimum CFM 
required when the fresh air duct is 
operating continuously.  

Press Up or Down to adjust the fresh 
air CFM.  Increasing the CFM to 210 
would lower the number of minutes 
per hour of fresh air operation 
allowing it to be accomplished during 
calls.  Press NEXT to continue.

The PDMi3 shows the number of 
minutes of fresh air operation each 
hour.  Press Up or Down to adjust the 
fresh air minutes each hour.  Press 
NEXT to continue to the next menu 
selection.

Fresh Air   Calc
             Y/N

Fresh Air  Enter
Min/Hr       Y/N

Change Fresh Air
Option       Y/N

Fresh Air    Off
      Y-On/N-Off

Area        2200
SqFt    U/D/NEXT

Bedrooms       4
        U/D/NEXT

Fresh Air     70
CFM     U/D/NEXT

Fresh Air     20
Min/Hr  U/D/NEXT

Fresh Air     20
Min/Hr  U/D/NEXT

Fresh Air    210
CFM     U/D/NEXT

Press Yes to select limiting upstaging 
based on outdoor temperature.

Staging is controlled by the number of minutes heating or 
cooling has been calling.  The Timer monitors the continuous 
call time and forces staging when the call time exceeds the 
preset limits.

Staging can be disabled if the outdoor temperature exceeds 
the preset limits. 

Limit Staging Based on Outdoor Temperature

Press Yes to select timed upstaging.

Press Up or Down to set the number 
of minutes of continuous call time 
required to upstage to Stage2. Press 
NEXT to continue.

Press Up or Down to set the number 
of minutes of continuous call time 
required to upstage to Stage3. Press 
NEXT to continue to the next menu 
selection.

Press Up or Down to set the outdoor 
temperature to disable staging 
heating.  If the outdoor temperature is 
above the limit, staging of heating is 
disabled.  Press NEXT to continue.

Press Up or Down to set the outdoor 
temperature to disable staging 
cooling.  If the outdoor temperature 
is below the limit, staging of cooling 
is disabled.  Press NEXT to continue 
to the next menu selection.

Staging Based on Call Timer

Timed
UpStaging    Y/N

Stage 2       20
Minutes U/D/NEXT

Stage 3       30
Minutes U/D/NEXT

Limit Staging
OD Temp      Y/N

OD Temp Lmt   60
Heating U/D/NEXT

OD Temp Lmt   55
Cooling U/D/NEXT

Summary of Contents for ProR212J

Page 1: ...nfigure a zone All panels operate with gas electric systems conventional heat pumps and dual fuel heat pumps Selected using the jumper plugs on the panel See table below See table below See table belo...

Page 2: ...ir damper is open LEDs indicate zone damper position Multi color LEDs indicate equipment call status Jumper plugs for selecting type of equipment Multi color LEDs indicate zoning panel status Terminal...

Page 3: ...n below 1 3 HVAC PANEL ZONE DAMPERS 1 1 2 2 3 FAD 3 THERMOSTATS Quick View ProR321J Zoning Panel ProZone Two 8 screws Two 8 screws Panel 3 Zone Maximum VA 40VA Transformer 60VA Transformer 75VA Transf...

Page 4: ...VAC Thermostat R C Y or Y1 G Zoning Panel R C 24VAC 24VAC Common Cooling Stage1 Indoor Fan Y G Terminal Function W1 OB Stage1 Heating W1 OB Inside Day Th MODE MENU FAN SYSTEM Schedule Auto Heat Heat S...

Page 5: ...AC EQUIPMENT W2 E Y2 R R O O B W1 B W Y Y1 Wiring HVAC Equipment Gas Electric System Two Stage Heat Gas Electric System Two Stage Cool Gas Electric systems using a single 24VAC transformer are wired a...

Page 6: ...ature Sensor Input Outdoor Temperature Sensor Input From Outdoor Temperature Sensor TS3 Terminal Function Discharge Air Temperature Sensor Model TS2 The optional discharge or leaving air temperature s...

Page 7: ...nd releasing the MENU key accesses the User menu where settings and data can be viewed but not changed 9 EXT PDMi MENU MENU NEXT NEXT SAVE SAVE PDM Programming Display Module PDM Programming Display M...

Page 8: ...and cooling the fan operation the supply air temperature limits outdoor changeover temperature for dual fuel heat pumps and number of zones being used Press No to continue Press Yes to change the siz...

Page 9: ...ing control The equipment type is set by the jumper plugs and cannot be changed with PDMi3 Press Yes to continue to select additional options Press Yes to select conventional heat pump If equipment ty...

Page 10: ...ats that can be used in that zone Press Up or Down to change the number of auxiliary heating stages Press NEXT to continue Press Up or Down to change the heating temperature limit Press NEXT to contin...

Page 11: ...he bypass position of the damper when it is being used for bypass Press Next to set the bypass position of the next damper Press Up or Down to adjust the bypass position of the damper when it is being...

Page 12: ...s NEXT to continue Press Yes to enter the minutes of fresh air operation required each hour Press No to select calculating the CFM and minutes per hour Press Yes to change the Fresh Air Option Press n...

Page 13: ...pposite system service The panel normally services heating or cooling calls based on the number of calls from the zones If there are more heating calls than cooling it will service heating and vice ve...

Page 14: ...t a test stage2 heating to insure discharge temperature is correct or return to the main menu if only one stage of heating is used Press Yes to start a bypass test A test will be started based on the...

Page 15: ...Press NEXT to go to the next letter in the name Press SAVE to save the clone name Monitor HVAC Performance Y N LAT 122 Prs 0 55 BP Pos 0 NEXT Press Yes to display the leaving air temperature duct pres...

Page 16: ...una Hills CA 92653 949 916 0945 Fax 949 458 8502 www ProZone US com Limited 5 Year Warranty The 5 year warranty is limited to the repair or replacement of defective product due to parts failure or def...

Reviews: