background image

Changing Zone Sizes

Selecting Type of Thermostat

Zone1

Zone2

Zone3

400 CFM

Zone CFM

3 x 400/1200

Calculate

Weighted Value

3 x 600/1200

3 x 200/1200

1.0 zones

Zone Size

1.5 zones

0.5 zones

3.0 zones

600 CFM

200 CFM

1200 CFM

Zones can be set to the same size or each zone can be set 
differently.  The size of the zones are in a weighted zone value.  
If zones are equal size, the weighted zone value is 1.0 zones.  
The examples below show a 3-zone installation with different 
zone sizes.

If gas/electric equipment is selected, only a heat/cool thermostat 
can be used in all zones.  If heat pump equipment is selected, a 
heat/cool or a heat pump type thermostat can be used in Zone1.  
Thermostats in Zones 2 and 3 are always heat/cool types.

Zone size is calculated by multiplying the total number of zones 
(3) by the zone CFM (400) divided by the total CFM (1200).  The 
calculation can also be done using square footage or percent 
demand.

Important!
The total of the zone sizes should always equal the total number 
of zones.

Press Yes to select the thermostat type  
used in each zone.

Press Yes to change the zone sizes or 
press NEXT to continue to next menu 
selection.

Press Yes to set all zone sizes the 
same or press No to set the size of 
each zone.

Press Up or Down to set the size of 
the zone.  Press NEXT to set the size 
of the next zone.

Press Up or Down to set the size of 
the zone.  Press NEXT to set the size 
of the next zone.

Press Up or Down to set the size of 
the zone.  Press NEXT to continue to 
the next menu selection.

Press Up or Down to change the 
number of stages.  Press NEXT to 
continue.

Press Yes to select the heat/cool 
thermostat for that zone.  Press No to 
see other thermostats that can be 
used in that zone.

Press Up or Down to change the 
number of auxiliary heating stages.  
Press NEXT to continue.

Press Up or Down to change the 
heating temperature limit. Press 
NEXT to continue.

Press Up or Down to change the 
outdoor temperature to switch to 
fossil fuel heating. Press NEXT to 
continue.

Press Up or Down to change the 
cooling temperature limit. Press 
NEXT to continue.

Press Up or Down to change the 
number of zones being used. Press 
NEXT to continue.

Equipment Type
DFHP         Y/N

Select Tstat
Options      Y/N

Change Zone Size
             Y/N

Are All Zones
Equal Size   Y/N

Zone  1      1.0
Size    U/D/NEXT

Zone  2      1.5
Size    U/D/NEXT

Zone  3      0.5
Size    U/D/NEXT

Compressor     1
Stages  U/D/NEXT

Zone 1 1Stg HC
Tstat        Y/N

Aux Heating    1
Stages  U/D/NEXT

Htg Temp Lmt 160
        U/D/NEXT

Fossil Fuel   35
OBP     U/D/NEXT

Clg Temp Lmt  45
        U/D/NEXT

Total Zones   3
Used    U/D/NEXT

10

There are a number of bypass methods that can be used with the 
panel as shown below.

If the ducts are sized for larger airflow and there is only 2 or 3 
zones, no bypass may be acceptable.  Or each zone damper 
can be set to not fully close.  The actuator has a cam that can 
set the closed position from fully closed to about 50% closed 
to provide some bypass.

If a mechanical bypass damper is being used with a bypass 
duct, select Ext Baro.  

The bypass damper must be sized to bypass the total system 
CFM minus the CFM of the smallest zone. The weights on the 
arm of the bypass damper should be set so the damper is 
fully open and open enough to eliminate any noise that may 
occur when only the smallest zone damper is open.

Bypass Control

No Bypass

Barometric Damper with Bypass Duct

With actuator in the Open position, 
loosen screw, rotate cam CW and 
tighten screw.

Model ProBMR-XX

Bypass Mechanical Damper 

Press Yes to select dual fuel heat 
pump. If equipment type is incorrect, 
press Cancel and see Selecting 
Equipment on page 3. 

Summary of Contents for ProR212J

Page 1: ...nfigure a zone All panels operate with gas electric systems conventional heat pumps and dual fuel heat pumps Selected using the jumper plugs on the panel See table below See table below See table belo...

Page 2: ...ir damper is open LEDs indicate zone damper position Multi color LEDs indicate equipment call status Jumper plugs for selecting type of equipment Multi color LEDs indicate zoning panel status Terminal...

Page 3: ...n below 1 3 HVAC PANEL ZONE DAMPERS 1 1 2 2 3 FAD 3 THERMOSTATS Quick View ProR321J Zoning Panel ProZone Two 8 screws Two 8 screws Panel 3 Zone Maximum VA 40VA Transformer 60VA Transformer 75VA Transf...

Page 4: ...VAC Thermostat R C Y or Y1 G Zoning Panel R C 24VAC 24VAC Common Cooling Stage1 Indoor Fan Y G Terminal Function W1 OB Stage1 Heating W1 OB Inside Day Th MODE MENU FAN SYSTEM Schedule Auto Heat Heat S...

Page 5: ...AC EQUIPMENT W2 E Y2 R R O O B W1 B W Y Y1 Wiring HVAC Equipment Gas Electric System Two Stage Heat Gas Electric System Two Stage Cool Gas Electric systems using a single 24VAC transformer are wired a...

Page 6: ...ature Sensor Input Outdoor Temperature Sensor Input From Outdoor Temperature Sensor TS3 Terminal Function Discharge Air Temperature Sensor Model TS2 The optional discharge or leaving air temperature s...

Page 7: ...nd releasing the MENU key accesses the User menu where settings and data can be viewed but not changed 9 EXT PDMi MENU MENU NEXT NEXT SAVE SAVE PDM Programming Display Module PDM Programming Display M...

Page 8: ...and cooling the fan operation the supply air temperature limits outdoor changeover temperature for dual fuel heat pumps and number of zones being used Press No to continue Press Yes to change the siz...

Page 9: ...ing control The equipment type is set by the jumper plugs and cannot be changed with PDMi3 Press Yes to continue to select additional options Press Yes to select conventional heat pump If equipment ty...

Page 10: ...ats that can be used in that zone Press Up or Down to change the number of auxiliary heating stages Press NEXT to continue Press Up or Down to change the heating temperature limit Press NEXT to contin...

Page 11: ...he bypass position of the damper when it is being used for bypass Press Next to set the bypass position of the next damper Press Up or Down to adjust the bypass position of the damper when it is being...

Page 12: ...s NEXT to continue Press Yes to enter the minutes of fresh air operation required each hour Press No to select calculating the CFM and minutes per hour Press Yes to change the Fresh Air Option Press n...

Page 13: ...pposite system service The panel normally services heating or cooling calls based on the number of calls from the zones If there are more heating calls than cooling it will service heating and vice ve...

Page 14: ...t a test stage2 heating to insure discharge temperature is correct or return to the main menu if only one stage of heating is used Press Yes to start a bypass test A test will be started based on the...

Page 15: ...Press NEXT to go to the next letter in the name Press SAVE to save the clone name Monitor HVAC Performance Y N LAT 122 Prs 0 55 BP Pos 0 NEXT Press Yes to display the leaving air temperature duct pres...

Page 16: ...una Hills CA 92653 949 916 0945 Fax 949 458 8502 www ProZone US com Limited 5 Year Warranty The 5 year warranty is limited to the repair or replacement of defective product due to parts failure or def...

Reviews: