11

 

7.1.4 Tube collector or start function

If this function is activated, the solar circuit pump is started for the entered time 

frame regardless of the actual collector temperature. This allows the medium to 

reach the measuring point to determine the collector temperature. 

"Basic Setup" menu 
Display

 Meaning

Value range Factory set-

ting

Line Value

4

1

Special function for the time-control-

led circulation when operating tube 

collectors

0 = Off  

1 = On

0 = Off

7.2 Protective functions

The controller is equipped with the following protective functions.

7.2.1 Collector protection

If the storage tank has reached the set maximum temperature and the collector 

temperature exceeds the set collector protection temperature (line 1), the solar 

circuit pump is switched on. The solar circuit pump is switched off once the collec-

tor temperature is 10K below the maximum value.
In this case, the storage tank is charged up to 95°C regardless of the set maximum 

temperature.

7.2.2 Recooling (Holiday function)

The collector protection function is only effective if the storage tank temperature is 

below the temperature limit (95°). Therefore, during the holiday period, for exam-

ple, the storage tank is discharged at night to the set recooling temperature.
Make sure not to activate this function together with the backup heating! 

"Basic Setup" menu 
Display

 Meaning

Value range Factory set-

ting

Line Value

0

0

Switches on or off the collector protec-

tion function

0 = Off  

1 = On

0 = Off

1

120 

°C

Temperature at which the collector 

protection function is activated 

110 –150°C

120°C

2

0

Switches on or off the recooling 

function (only if the collector protec-

tion is on)

0 = Off  

1 = On

0 = Off

3

40°C

Temperature to which the storage 

tank is recooled once the collector 

protection function is activated

30 –90°C

40°C

 

Settings and changes in 
this menu must only be 

carried out by a specialised 
technician. Incorrect settings can 
damage or adversely affect the 
function of the solar power system.

 

Settings and changes in 
this menu must only be 

carried out by a specialised 
technician. Incorrect settings can 
damage or adversely affect the 
function of the solar power system.

Summary of Contents for Solareg II ENERGY

Page 1: ...Microcontroller controlled temperature difference controller for solar thermal systems Operatingmanual Solareg II ENERGY...

Page 2: ...7 1 4 Tube collector or start function 11 7 2 Protective functions 11 7 2 1 Collector protection 11 7 2 2 Recooling Holiday function 11 7 2 3 System protection 12 7 3 Additional function 12 7 3 1 Ene...

Page 3: ...ection recooling and flow monitoring Generous wiring space Available accessories Temperature sensor PT1000 Yield measurement set incl tube sensor Sensor connection box Immersion sleeves 2 Safety instr...

Page 4: ...opened 3 2 Wall mounting The device is mounted on the marked points A drilling template is provided with the device Insert the Quick Info card provided with the device into the pocket provided on the...

Page 5: ...ors 2 sensors are required the third sensor is optional Mounting wiring the temperature sensors Mount the sensors on the collector and the storage tank Ensure proper heat transfer and use heat conduct...

Page 6: ...decreases continuously Scroll right Select Confirm Scroll right in the main menu Select a menu item Confirm a value change and store it 5 Menu structure 5 1 Info menu The following measured and yield...

Page 7: ...fer ence 2 35K 3K min 100 12 Set the minimum pump capacity using the RPM control 100 RPM control off 30 100 100 40 C Switch on tem perature for the thermostat func tion 20 90 C 40 C dT 10 K Hysteresis...

Page 8: ...f 1 On 0 Off 1 120 C Collector protection function 110 150 C 120 C 2 0 Recooling function only if the collector protection is on 0 Off 1 On 0 Off 3 40 C Recooling temperature 30 90 C 40 C 4 0 Tube col...

Page 9: ...30V connections L Mains phase N Neutral conductor mains and outputs A1 Solar circuit pump switching output 1 A2 Switching output 2 Sensor connections S1 Collector sensor S2 Lower storage tank S3 Therm...

Page 10: ...s place when under the preset temperature Basic Setup menu Display Meaning Value range Factory set ting Line Value 6 1 The cooling or thermostat function can also be selected 0 Off 1 Cooling 2 Heating...

Page 11: ...ecooling Holiday function The collector protection function is only effective if the storage tank temperature is below the temperature limit 95 Therefore during the holiday period for exam ple the sto...

Page 12: ...enu Display Meaning Value range Factory set ting Line Value 5 0 Switches on or off the energy yield measurement function 0 Off 1 On 0 Off 8 System monitoring If an error occurs the flashing symbol is...

Page 13: ...ce sensor if necessary Flashing Short circuit in the sensor cable Check cable Defective sensor Check sensor resistance and replace sensor if nec essary Circulation error No flow Flashing Additional di...

Page 14: ...ircuits Defect device Contact the supplier Outputs are not switched on Controller is in manual operation Exit Manual operation Switch on condition is not satisfied Wait until switch on condition is sa...

Page 15: ...min according to EN 60730 DIN VDE 0631 IEC 60664 IEC Output Voltage Power switching output 230V 1A approx 230VAfor cos 0 7 1 0 Fuse protection Fine wire fuse 5 x 20mm 2A T 2 amperes delayed action fus...

Page 16: ...eduction of price is excluded Warranty claims may only be submitted by the customer and are non transferable If a defect occurs during the warranty period please contact the supplier installer When re...

Reviews: