6.  For OA2POAFF1860100BL 2-position outside air package, route actuator wiring through the 

two ties found under the control box. 

(ILL. 2)

  Additional wire clamps are provided for securing 

wire after completion, if needed

 

Route actuator wiring through prepunched grommet into control box. 

(ILL. 2) 

 

Connect actuator wiring to terminal block in control box. (

ILL. 3

)

 

The actuator is factory set to minimum open position.  To increase open position, loosen set 
screw on limitor of actuator (Be careful not to remove screw completely.  Just loosen.).  Move 
limitor to desired open position and secure set screw. (

ILL. 4

)

ILL. 3

ILL. 4

Fully Open Position

Minimum 

Open 

Position

(Factory 

Set)

Limitor

O C R G

W2

Y

Transformer

Terminal Block

On Unit Fan Control

Air Conditioning Unit

Red

Black

To Room Thermostat

Actuator

Fan Relay

24V

PLEASE NOTE:  
If the unit is 208/230V, single phase, 
power supply, the installed 40VA 
transformer may need to be replaced 
with a 75VA transformer and circuit 
breaker.  All other factory units 
have the 75VA transformer installed 
standard.