 Water Piping

This appliance is suitable for potable water and space heating applications. Do not use this appliance if any part has
been underwater.  Immediately call a qualified service technician to inspect the appliance and replace any part of the
control system and gas control which has been under water.

If the water heater is installed in a closed water supply system, such as one having a backflow preventer in the cold
water supply line, means shall be provided to control thermal expansion. Contact the water supplier or a local plumb-
ing inspector on how to control this situation.

A pressure relief valve must be installed near the hot water outlet that is rated in accordance with and complying with
either The Standard for Relief Valves and Automatic Shutoff Devices for Hot Water Supply Systems, ANSI Z21.22, or
The ANSI/ASME Boiler and Pressure Vessel Code, Section IV ( Heating Boilers ). This pressure relief valve must
be capable of an hourly Btu rated temperature steam discharge of 250,000 Btuh. Multiple valves may be used. The
pressure relief capacity must not exceed 150 psig. No valve shall be placed between the relief valve and the water
heater. The relief valve must be installed such that the discharge will be conducted to a suitable place for disposal
when relief occurs. No reducing coupling or other restriction may be installed in the discharge line. The discharge line
must be installed to allow complete drainage of both the valve and the line. If this unit is installed with a separate
storage vessel, the separate vessel must have its own temperature and pressure relief valve. This valve must also
comply with The Standard for Relief Valves and Automatic Gas Shutoff Devices for Hot Water Supply Systems, ANSI
Z21.22. (in the U.S. only). A temperature relief valve is not required, but if one is used, do not install the valve with the
probe directly in the flow of water. This may cause unwarranted discharge of the valve.

Piping and components connected to the water heater shall be suitable for use with potable water.
Toxic chemicals, such as those used for boiler treatment, shall not be introduced into the potable water.
A water heater used to supply potable water may not be connected to any heating system or components previously
used with a nonpotable water heating appliance.
When water is required in one part of the system at a higher temperature than in the rest of the system, means such
as a mixing valve shall be installed to temper the water to reduce the scald hazard.

Installation and service must be performed by a qualified plumber.  In the
Commonwealth of Massachusetts, this product must be installed by a licensed
plumber or gas fitter in accordance with the Massachusetts Plumbing and Fuel
Gas Code 248 CMR Sections 2.00 and 5.00. Observe all applicable codes.

• Flush water through the pipe to clean out metal powder, sand and dirt before connecting it.
• Perform the following insulation measures for prevention of freezing.

• Take appropriate heat insulation measures (e.g., wrapping with heat

insulation materials, using electric heaters) according to the climate of
the region to prevent the pipe from freezing.

• Make sure that there are no water leaks from the cold and hot water

supply pipes, then insulate the pipes completely.

• Be sure to also completely insulate the water supply valve and the

cold and hot water connections on the water heater (refer to the figure
on the right).

• Do not cover the water drain plug with insulation so that water in the

pipe can be drained. (Refer to the figure in the right.)

• Use a union coupling or flexible pipe for connecting the pipes to reduce the force applied to the piping.
• Do not use piping with a diameter smaller than the coupling.
• When feed water pressure is too high, insert a depressurizing valve, or take water hammer prevention measure.
• Avoid using joints as much as possible to keep the piping simple.
• Avoid piping in which an air holdup can occur.
• If installing the unit on a roof:
• About lower-level hot water supply

If the unit is installed on a roof to supply water to the levels below, make sure that the water pressure supplied to
the unit does not drop below 29 psi. It may be necessary to install a pump system to ensure that the water pressure
is maintained at this level.
Check the pressure before putting the unit into operation.
Failure to supply the proper pressure to the unit may result in noisy operation, shorter lifetime of the unit, and may
cause the unit to shut down frequently.

Completely insulate  
the water inlet and  
outlet fittings. 

Insulate the water  
supply valve completely.

Do not cover the water  
drain plug with insulation   
so that water in the pipe  
can be drained.

Summary of Contents for NR111-OD

Page 1: ...y and follow the installation instructions Failures and damage caused by erroneous work or work not as instructed in this manual are not covered by the warranty Check that the installation was done properly in accordance with this Installation Manual upon completion After completing installation please either place this Installation Manual in a plastic pouch and attach it to the side of the water ...

Page 2: ...rd 10ft 1 2 Optional Accessories The accessories listed below are not included with the units but may be necessary for installation Cross Recessed Head Screw Quick Connect Cord Q ty Shape Part Part Shape Q ty 1 1 Remote Controller Cord 26ft 1 Isolation Valves includes pressure relief valve Pipe Cover PC 3S 1 1 Recess Box RB 900 1 Remote Controller Outdoor Junction Box Owner s Guide Warranty Instal...

Page 3: ...ween the two units When connecting two units use only a single remote controller Note Connect the remote controller to only one of the units System Diagram Insulate the hot water piping to prevent heat loss Insulate and apply heating materials to the cold water supply piping to prevent heat loss and freezing of pipes when exposed to excessively cold temperatures Union Make this distance as short a...

Page 4: ... pan adequately drained be installed under the appliance The pan must not restrict combustion air flow Check the Gas Check that the rating plate indicates the correct type of gas Check that the gas supply line is sized for 250 000 Btuh for this unit Check the Power The power supply required is 120VAC at 60Hz May result in fire or electric shock Use Extreme Caution if Using With a Solar Pre Heater ...

Page 5: ... heat Also consider the surrounding trees and animals The heat and moisture from the water heater may cause discoloration of walls and resinous materials or corrosion of aluminum materials Do not locate the vent termination directed towards a window or any other structure which has glass or wired glass facing the termination Install in a location where the exhaust gas flow will not be affected by ...

Page 6: ... in width Provide clearance of 24 or more in front of the unit to facilitate inspection and repair Do install the unit such as the wall of the second floor where the unit is out of reach When installing the unit in a common side corridor pro vide a clearance of 47 or more in front of the unit Set the bottom edge of the exhaust port about 84 from the corridor floor Handrail common side corridor bal...

Page 7: ...tion air inlet to any other appliance K Clearance to a mechanical air supply inlet 6 ft 1 83 m L Clearance above paved sidewalk or paved driveway located on public property Clearance under veranda porch deck or balcony 7 ft 2 13 m M 1 In accordance with the current CSA B149 1 Natural Gas and Propane Installation Code 2 In accordance with the current ANSI Z223 1 NFPA 54 National Fuel Gas Code A ven...

Page 8: ...sary force to the device when installing Internal parts may be damaged and may become highly dangerous Install the unit on a vertical wall and ensure that it is level Locating Screw Holes Mounting Structure When installing with bare hands take caution to not inflict injury Be careful not to hit electrical wiring gas or water piping while drilling holes Item CAUTION Be sure to do Mounting Bracket u...

Page 9: ... line consult local codes or the National Fuel Gas Code ANSI Z223 1 Natural Gas Meter See next page for the pipe capacity charts Noritz Tankless Gas Water Heater 250 000 Btuh Clothes Dryer 35 000 Btuh Barbecue 50 000 Btuh Gas Range Stove 65 000 Btuh 10 10 10 10 5 5 5 5 Gas Fireplace 25 000 Btuh Instructions 1 Size each outlet branch starting from the furthest using the Btuh required and the length...

Page 10: ... in Cubic Feet per Hour of Natural Gas 0 60 Specific Gravity 0 5 WC Pressure Drop Length in Feet Pipe Size 3 4 1 1 1 4 1 1 2 2 10 20 30 40 50 60 70 80 90 100 150 200 206 383 614 1261 2934 147 269 418 888 2078 121 218 334 723 1698 105 188 284 625 1472 94 168 251 559 1317 86 153 227 509 1203 80 141 209 471 1114 75 132 194 440 1042 71 125 181 415 983 67 118 171 393 933 55 94 137 320 762 48 82 116 277...

Page 11: ...stem or components previously used with a nonpotable water heating appliance When water is required in one part of the system at a higher temperature than in the rest of the system means such as a mixing valve shall be installed to temper the water to reduce the scald hazard Installation and service must be performed by a qualified plumber In the Commonwealth of Massachusetts this product must be ...

Page 12: ...er resistance Use shower heads with low pressure loss If necessary use a pump or other means to en sure that the supply water pressure to the inlet of the heater does not fall below 29 PSI when the maximum amount of water is being demanded Also install a pressure meter on the inlet If this is not done local boiling will occur inside the water heater causing abnormal sounds and decreasing the durab...

Page 13: ...L Treatment Required Treatment Required Treatment Required Install Noritz Isolation Valves to allow for flushing Flushing is required if a water treatment device is not installed Suggested Suggested Install Noritz Isolation Valves to allow for flushing Flushing is required if a water treatment device is not installed Residential Use Treatment Guidelines Commercial Use Treatment Guidelines If this ...

Page 14: ...e used to control the pump 3 Use an Aquastat if the water heater is not control ling the pump Set the Aquastat to 10 F below the set output temperature 4 Noritz recommends the use of an Isolation Kit with the installation These kits include an integrated shut off and serv ice valve with unions and a pressure relief valve Optional Expansion Tank 6 NORITZ Tankless Gas Water Heater NORITZ Tankless Ga...

Page 15: ...he water heater Putting the redundant length of cord inside the water heater may cause electrical interference and faulty operation Disconnect Power Electrical Shock Hazard Do not turn power on until electrical wiring is finished Disconnect power before servicing Failure to do so may result in death or serious injury from electrical shock WARNING Electrostatic discharge can affect electronic compo...

Page 16: ...rs on the display 3 Set the upper limit of the hot water supply temperature to 125 F 130 F 135 F or 140 F using the UP and DOWN setting buttons 4 To put the water heater back into operation press the ON OFF button on the remote controller To keep the water heater off let the unit sit for 30 sec to return to the original display When setting the maximum temperature to 125 180 F 1 Turn the water hea...

Page 17: ...e and cause problems Be sure to hand tighten when screwing to the terminal block Power tools may cause damage to the terminal block 1 Check to make sure that the remote controller cord has plenty of slack in order to reach the external connection terminal block 2 Disconnect electrical power to the water heater 3 Remove the single screw securing the terminal block cover and then remove the cover 4 ...

Page 18: ...om a wall circuit to the pump 5 Replace the front cover Pump Wiring This feature is not available when using the Quick Con nect Multi System feature Relay connection with larger pumps 85 W 1 Locate and prepare the pump control wires as described above 2 Choose a suitable installation location for the relay where it will be protected from moisture 3 Connect the pump control wires from the heater to...

Page 19: ... 4 Green 5 Blue 6 Blue 1 Red 2 Black 3 White 4 Green 5 Blue 6 Blue 1 Red 2 Black 3 White 4 Green 5 Blue 6 Blue 1 White 2 Green 3 Red 4 Black 5 Blue 6 Blue Connecting the Quick Connect Cord to the two units 1 Turn off the power 2 Remove the front cover of the heater 4 screws 3 Pass the Quick Connect Cord through the wiring throughway and into the unit 4 Plug the connector on the Quick Connect Cord ...

Page 20: ...or a proper blue color and consistency If the flame does not appear normal the burner may need to be cleaned If the burner needs to be cleaned it must be performed by a qualified service technician Do not obstruct the flow of combustion and ventilation air The pressure relief valve must be operated once a year to ensure that it is functioning properly and there is no obstruction Turn the power off...

Page 21: ...power to the unit 8 The unit will now operate whenever hot water is called for If the unit will not operate follow the shutdown instructions and call a service technician Shutdown Instructions 1 Stop any water demand 2 Turn off electric power 3 Turn the gas control manual valve clockwise to the off position Should overheating occur or the gas supply fail to shut off turn off the manual control val...

Page 22: ...9 6 1 11 5 3 5 4 14 4 6 3 6 9 2 9 GAS INLET 3 4 120VAC 4 0 5 6 0 24 x 0 4 OBLONG HOLE 4 0 5 6 0 24 x 0 4 OBLONG HOLE HEIGHT OF EACH FITTINGS FROM BOTTOM OF CASE WATER OUTLET WATER INLET FLUE COLLAR WIRING THROUGHWAYS WATER DRAIN VALVE WATER FILTER HOT WATER OUTLET WATER DRAIN VALVE WIRING THROUGHWAY 120VAC COLD WATER INLET HOT WATER OUTLET 3 4 WIRING THROUGHWAYS COLD WATER INLET 3 4 VIEW FROM TOP ...

Page 23: ...Notes on the Installation Location The remote should be installed in an easily accessible location Avoid installing in a place where water or steam can come into contact with the controller Avoid locations where special chemical agents e g benzene fatty and oily deter gents are used Avoid outdoor installation or installation in an indoor location where it will be exposed to direct sunlight Connect...

Page 24: ...cord Phillips Roundhead Wood Screw Wall Anchor 3 Remove the cover of the remote control mark the location of the screw holes and drill holes for the wall anchors 4 Insert the wall anchors screw the remote control to the wall and replace the cover Remote Controller Cord Wall Packing take off the paper Remote Control Wires Rear Side of Remote Controller ...

Page 25: ...the wall pipe containing the remote controller wires through the hole 4 Slide the junction box packing and the junction box over the remote controller wires and wall pipe protruding from the outside wall Wall packing Wall pipe Take out the pipe about 3 4 from the wall Junction Box Box Nut Junction Box Packing Take off the paper 5 Slide the box nut over the remote controller wires and screw it onto...

Reviews: