Module Configuration
MVI46-S3964R
♦
SLC Platform
Siemens 3964R Protocol
ProSoft Technology, Inc.
Page 25 of 74
This parameter assigns a name to the module that can be viewed using the
configuration/debug port. Use this parameter to identify the module and the
configuration file.
2.4 [Backplane
46]
This section identifies the method of failure for the communications for the
module if the processor is not in run.
The following example shows a sample [Backplane Configuration] section:
[Backplane 46]
Backplane Fail Count : 10 #Number of consecutive backplane transfer failures
# before halting communications
2.4.1 Backplane Fail Count
0 to 65535
This parameter specifies the number of consecutive backplane transfer failures
that can occur before communications should be halted.
2.5
[3964R Port x]
# This section is used to define the port 1 configuration for the 3964R device
[3964R Port 1]
Enable : Yes #No=Port Disabled,Yes=Port Enabled
Baud Rate : 9600 #Baud rate for port (300, 600, 1200, 2400, 4800,
#9600, 19200, 38400, 57600, 115)
Parity : Even #N=None,O=Odd,E=Even
Data Bits : 8 #7 or 8 data bits for messages
Stop Bits : 1 #1 or 2 stop bits for messages
RTS On : 0 #Delay after RTS set before message sent (mSec)
RTS Off : 0 #Delay after message before RTS dropped (mSec)
Minimum Response Delay: 0 #Delay before responding to CP
Use CTS Line : No #Monitor CTS modem line (Y/N)
Swap : 1 #0=No Data Byte Swapping, 1=Data Byte Swapping
Priority : 0 #0=High Priority, 1=Low Priority
Protocol : 0 #0=3964 RK512, 1=3964
ACK Delay : 1000 #Number of mSec to wait for ACK (Default 1000ms)
Setup Attempts : 6 #Number of times to try to connect to CP
#(Default 6)
Transmit Attempts : 6 #Number of times to try to transmit to CP
#(Default 6)
2.5.1 Enable
Yes or No
This parameter specifies whether to enable or disable the port. No = Port
Disabled, Yes = Port Enabled.