5604-RIO-PDPMV1
♦
ProLinx Standalone
Verify Data Exchange
Rockwell Automation® Remote I/O to PROFIBUS DP-V1 Master Gateway
Page 32 of 45
ProSoft Technology, Inc.
November 20, 2008
2
Double-click the command. This action opens the Edit dialog box.
For this command, the module will check database register 1806. If the value
at register 1806 is non-zero (the Count value), the module will send the data
at register address 2600 to the PROFIBUS network.
This register corresponds to register N16:806 in the PLC5 processor. To
trigger the command, change the value of register N16:806 from 0 to 1. This
value is immediately transmitted from the PLC5 processor to the 5604-RIO-
PDPMV1 module.