Technical Specifications
Page 63 of 69
6.4.
DF1
Specification
Rating
Connector
4-way terminal
Conductor
24 to 18 AWG
Isolation voltage
2.5 kV
Protocol
DF1 Full Duplex, DF1 Half Duplex, DF1 Radio Modem
BAUD
1200, 2400, 4800, 9600, 19200, 38400, 57600, 115200
Parity
None, Even, Odd
Data bits
8
Stop bits
1
Error detection
CRC, BCC
Embedded response
Auto, On
DF1 Slave mode
Max 20 mapping items
Scheduled Tag mode
Max 20 mapping items
DF1 Slave Mode Message
Support
PLC-5 Typed Read, PLC-5 Typed Write, SLC Typed Read, SLC Typed Write, PLC-
2 Unprotected Read, PLC-2 Unprotected Write, PLC-2 Unprotected Bit Write
Scheduled Tag Mode
Message Support
PLC-5 Typed Read, PLC-5 Typed Write, SLC Typed Read, SLC Typed Write
Table 6.3 - DF1 specification
6.5.
CERTIFICATIONS
Certification
ATEX: Zone 2 Cat 3
CB Safety
CE
UL/cUL Class 1 Div 2
Table 6.4 – Certifications
THIS EQUIPMENT IS AN OPEN-TYPE DEVICE AND IS MEANT TO BE INSTALLED IN AN
ENCLOSURE SUITABLE FOR THE ENVIRONMENT SUCH THAT THE EQUIPMENT IS ONLY
ACCESSIBLE WITH THE USE OF A TOOL.
SUITABLE FOR USE IN CLASS I, DIVISION 2, GROUPS A, B, C AND D HAZARDOUS
LOCATIONS, OR NONHAZARDOUS LOCATIONS ONLY.