8.2
Technical Data - PROFIBUS
Parameter
Description
Maximum number of cyclic input data
244 bytes
Maximum number of cyclic output data
244 bytes
Maximum number of acyclic data (read/write)
240 bytes/telegram
Maximum number of modules
24
Configuration data
Max. 244 bytes
Parameter data
237 bytes application specific parameters
Acyclic communication
DP V1 Class 1 Read/Write
DP V1 Class 1 Alarm
DP V1 Class 2 Read/Write/Data Transport
Baud rate
9.6 kBits/s, 19.2 kBits/s, 31.25 kBits/s, 45.45 kBits/s, 93.75 kBits/s,
187.5 kBits/s, 500 kBits/s, 1.5 MBits/s, 3 MBits/s, 6 MBits/s, 12
MBit/s
Auto baudrate detection is supported
Data transport layer
PROFIBUS FDL
Limitations
SSCY1S
– Slave to slave communication state machine not
implemented.
Data exchange broadcast not implemented.
Configuration by database not implemented yet.
I&M LR services other than Call-REQ/RES are not supported yet.
Reference to firmware/stack version
V2.7.x.x