3.6
Master Command Structure
Parameter
Description
Enable
0 = Disable
1 = Enable the Command: Polling and Trigger allowed.
2 = Enable the Command: Only Trigger allowed.
Node
Node address of the target device on the network (1 to 255).
Function
Function code for the command. 1, 2, 3, 4, 5, 6, 15 and 16 allowed
for Master and Slave. 8 allowed for Slave only.
DeviceAddress
Address in remote device associated with the command (0 to
65535).
Count
Number of points associated with the command.
InternalAddress
PLC Tag Internal address associated with the command.
PollInterval
Minimum number of milliseconds between issuance of command
(0 to 2,147,483,647).
Swap
0 = None. No change is made in byte ordering.
1 = Words
– The words are swapped.
2 = Words & Bytes
– The words are swapped, and then the bytes
in each word are swapped.
3 = Bytes
– The bytes in each word are swapped. The words
should be swapped only when using an even number of words.
Trigger
1 = Trigger the message. Can be triggered anytime the command
is enabled.