Logical states of the digital outputs:
Input
Signal description
Logical state
✻
State description
DQ A.0
Ready for operation
0
Ultromat not ready
1
Ultromat ready
DQ A.1
Dry run
0
Dry run (chamber 3 is empty)
1
Chamber 3 is full
DQ A.2
Collective alarm
0
No collective alarm
1
Collective alarm active
DQ A.3
Horn
0
Horn off
1
Horn on
DQ A.4
Solenoid valve
0
Solenoid valve closed
1
Solenoid valve open
DQ A.5
Stirrer 1
0
Stirrer (1) off
1
Stirrer (1) on
DQ A.6
Stirrer 2
0
Stirrer (2) off
1
Stirrer (2) on
DQ A.7
Heating
0
Heater off
1
Heater on
DQ B.0
Vibrator
0
Vibrator off
1
Vibrator on
DQ B.1
Motorised ball valve
(Batching, extraction)
0
Batching = closed
Extraction = open
1
Batching = open
Extraction = closed
✻
) 1 = 24 VDC; 0 = 0 VDC