16
Systems / data sheets
16.1 Logical states
Logical states of the digital inputs:
Input
Signal description
Logical state
✻
State description
DI A.0
Turbodos
-
DI A.1
Fault voltage 230 V
1
Voltage OK
0
Fault
DI A.2
Fault voltage 24 V
1
Voltage OK
0
Fault
DI A.3
Fault stirrer
1
Stirrer OK
0
Fault
DI A.4
Remote Operation
1
Remote control not active
0
Remote control active
DI A.5
Redilution pump
1
Transfer pump on (water supply avail‐
able)
0
Transfer pump off (water supply avail‐
able)
DI A.6
Redilution flow monitor
1
Flow present
0
Flow not present
DI A.7
Motorised ball valve batching
1
Motorised ball valve open
0
Motorised ball valve closed
DI B.0
Lack of powder dry feeder
1
Powder present
0
Powder not present
DI B.1
Overflow wetting cone
1
Wetting cone OK
0
Wetting cone overflow
DI B.2
Float switch liquid concentrate
1
Liquid concentrate present
0
Liquid concentrate empty
DI B.3
Liquid concentrate flow monitor
1
Liquid concentrate flow present
0
Liquid concentrate flow not present
DI B.4
Liquid concentrate pump fault
1
Liquid concentrate pump OK
0
Liquid concentrate pump fault
DI B.5
Motorised ball valve discharge
1
open
0
closed
✻
) 1 = 24 VDC; 0 = 0 VDC
Systems / data sheets
76