The following instructions are for a standard or
“common” recovery procedure.
setup procedure
1. Place the RG6000 unit on a flat, level surface.
2. Verify a clean filter screen is installed behind
the inlet fitting.
3. Connect a hose from the outlet fitting of the
unit to the liquid port on the recovery cylinder.
4. Connect a hose from the inlet fitting of the unit
to the output port of a manifold gauge set.
Promax recommends using a sight glass and a
filter / drier in this line.
5. Connect a hose from the liquid (low pressure)
side of the manifold gauge set to the liquid side
of the system being serviced.
6. Connect a hose from the vapor (high) side of
the manifold gauge set to the vapor side of the
system being serviced.
RG6000-KT only:
Attach tank connection
harness (No. 549977) to float switch
connection on the recovery cylinder.
7. Verify the inlet and outlet valves on the
RG6000 unit are closed.
8. Place the recovery cylinder on a scale (such as
TIF9010A) to avoid overfilling the cylinder.
S
tandard
o
Perating
i
nStructionS
Manifold
Gauge set
system Being
serviced
Inlet
Fitting
Outlet
Fitting
Float switch
Connection
(RG6000-KT only)
liquid
vapor
scale
Recovery
Cylinder
sight
Glass
Filter / drier
Tech Tips
The RG6000 will perform at its peak when voltage
entering the machine (while operating) is between
115V AC and 122V AC. Lower supply voltages
may result in difficulty starting under high head
pressure, reduced performance, and / or motor
overheating.
Use an outlet that does not have other applicances
(such as lights, machines, etc.) plugged into it.
Do not use an extension cord unless needed. If
an extension cord is used, it must be 14 AWG
minimum and as short as possible to reduce
voltage drops.
WARNING : A storage cylinder is full when
it reaches 80% volume. dO NOT OveRFIll. due
to liquid expansion, the cylinder could explode
if filled to more than 80% volume, possibly
causing personal injury and equipment damage.
liquid port