Promax RG6000 Operating Manual Download Page 1

1

Refrigerant Recovery Machine

Operating Manual

RG6000

TM

Manuel d’utilisation

Bedienungsanleitung

Manual de operaciones

Summary of Contents for RG6000

Page 1: ...1 Refrigerant Recovery Machine Operating Manual RG6000 TM Manuel d utilisation Bedienungsanleitung Manual de operaciones...

Page 2: ...four air changes per hour If accidental system discharge occurs ventilate the work area before resuming service USE THE SHORTEST POSSIBLE EXTENSION CORD WITH A MINIMUM size OF 14 AWG Using an undersiz...

Page 3: ...Liquid Recovery 7 Vapor Recovery 8 Purge Non Condensable Gas from a Storage Cylinder 8 Recovery Cylinder Information 9 Troubleshooting 10 Replacement Parts 11 Rebuild Kits and Accessories 12 Maintenan...

Page 4: ...5001 with this unit After the kit is installed and used with a recovery cylinder having an internal float switch the unit automatically shuts down when the cylinder is 80 full Your unit is pre wired...

Page 5: ...lves on the RG6000 unit are closed 8 Place the recovery cylinder on a scale such as TIF9010A to avoid overfilling the cylinder Standard Operating Instructions Manifold Gauge Set System Being Serviced...

Page 6: ...erating Instructions Recovery Procedure 1 Connect the unit to a 115V outlet 2 Slowly open the liquid valve of the recovery cylinder while watching hoses and connections for leaks 3 Set the recover pur...

Page 7: ...e from the outlet fitting of the unit to the vapor port on the system being serviced 3 Connect a hose from the inlet fitting of the unit to the vapor port of a recovery cylinder Promax recommends usin...

Page 8: ...r manifold gauge set in the hose setup 1 Allow the storage cylinder to sit undisturbed for 24 hours to allow air to rise to the top 2 Connect a manifold gauge set to the cylinder Read the amount of pr...

Page 9: ...led with liquid over 80 of volume The remaining 20 is called head pressure room Do not exceed 80 of cylinder capacity PROMAX recommends the use of the TIF9010A Refrigerant Scale for monitoring cylinde...

Page 10: ...ut hoses for restrictions or kinks Reduce head pressure Slow recovery 1 Trapped liquid in system 2 Restriction in refrigerant flow path 1 Momentarily cycle system compressor to move trapped refrigeran...

Page 11: ...are 12 551628 1 Power Cord 13 SK 6012 1 Bezel Kit includes bezel power switch circuit breaker power entry module hardware 14 SK 6001 1 Inlet Fitting Filter Screen Kit includes inlet fitting filter scr...

Page 12: ...lve Rebuild Replacement Kit includes inlet oulet valves and springs o rings SK 6008 Fan Replacement Kit SK 6012 Bezel Replacement Kit SK 6014 Condenser Replacement Kit SK 6015 Piston Seal Rebuild Kit...

Page 13: ...ct the RG6000 from the power supply before performing maintenance Burned out System 1 Use two high acid capacity filter driers in series when recovering from a burned out system Promax recommends Alco...

Page 14: ...d un an compter de la date d achat Toutefois les restrictions suivantes s appliquent 1 Cette garantie est non transf rable Toute r clamation au titre de la garantie doit tre soumise durant la p riode...

Page 15: ...ered in the USA Manufactured in China Con u et mis au point aux tats Unis Fabriqu en Chine Entworfen und entwickelt in den USA Hergestellt in China Dise ado en EE UU Fabricado en China Owatonna MN 550...

Reviews: