background image

 

4

 

 
Theory of operation- 

Why you need a ProSafe Isolation Transformer

 

 

When properly installed and connected, the ProSafe Isolation Transformer will provide isolation 
between shore and boat power while maintaining a one to one turns ratio, meaning the shore 
voltage is equal to boat voltage. 

 

This is a high quality product, however, it is possible to unknowingly abuse or  
misapply a transformer, therefore reducing its life expectancy. These installation and operation 
instructions set out the guidelines for peak performance of the ProSafe Isolation Transformer. 
The information contained in this manual outlines for the user the proper inspection, installation 
and maintenance required of these transformers. 

 

With the ProSafe Isolation Transformer, a boat’s electrical system and common grounding 
conductor are not connected to the shore-side system. Power is transferred from the shore-side 
electrical system to the boat’s electrical system by magnetic coupling. Specifically, this means 
there is no direct electrical connection between the shore-side, earth-grounded AC power and 
the boat’s AC power systems. The shore grounding is connected to a shield that is placed 
between the primary (shore) and secondary (boat) transformer windings. This shield ensures 
isolation of the boat because of its placement between the primary and secondary windings 
within the transformer. In the unlikely but possible event a breakdown occurs within the ProSafe 
Isolation Transformer, the shield can bear the fault current of a properly sized shore supply 
circuit breaker long enough for the breaker to trip. 

 

Properly installed, the ProSafe Isolation Transformer will electrically isolate AC shore power 
from the boat’s AC power system, reducing galvanic corrosion due to a direct AC shore power 
connection. This occurs because grounding one leg of the transformer secondary on board the 
boat results in the establishment of a “neutral” ground. When the ProSafe Isolation Transformer 
is properly installed, shoreline polarity is no longer a concern and the use of a galvanic isolator 
is not needed. 

 

Additionally, ProSafe Isolation Transformers are engineered to supply superior line noise 
reduction and spike suppression, providing high quality AC power from less than perfect power 
sources.  

 

TRANSFORMER DESIGN FOR SOUND REDUCTION 

 

ProSafe Isolation Transformers are “sound-controlled” in construction so that sound levels 
consistent with industry standards are achieved. Transformer coils are precision wound under 
measured constant tension to insure continual, vibration-free performance. Low noise levels in 
the core are maintained by using specially designed clamps for bolting the core into a tight 
unified assembly. All clamping bolts are tightened to an optimum torque level. Additional sound 
reduction is realized by impregnation with polymerizing varnish cured by a special baking 
process. Cabinet styles have their core and coils mounted to the cabinet on neoprene pads for 
reduction of conducted sound. The case is formed and assembled using dampening agents to 
reduce transmitted sound. The result is ultra quiet operation for the user. 

Summary of Contents for 411-SA02-036

Page 1: ... this manual for proper installation and operation instructions of this device It is essential for the safety of your boating family and other boating families around you that this product be properly installed For all Product Installation or Service questions please call ProMariner direct at 1 800 824 0524 Eastern Time 8 30am 5 00pm ...

Page 2: ...duct Overview pages 1 2 Introduction page 3 Theory of Operation page 4 Installation Warnings page 5 Installation Operating Safety page 6 Wiring Diagrams pages 7 17 Maintenance pages 18 19 Customer Service and Warranty page 20 ...

Page 3: ...stand without breakdown a high potential test of 4000 volts AC 60Hz for one minute applied between the shield and all other components such as windings core and outside enclosure 11 9 1 2 A separate insulated wire lead or terminal identified as the shield connection is to be solidly connected only to the shield and brought out for external connection and shall be equal to or greater than the aggre...

Page 4: ...rmer the shield can bear the fault current of a properly sized shore supply circuit breaker long enough for the breaker to trip Properly installed the ProSafe Isolation Transformer will electrically isolate AC shore power from the boat s AC power system reducing galvanic corrosion due to a direct AC shore power connection This occurs because grounding one leg of the transformer secondary on board ...

Page 5: ... described on the label found on the inside of the transformer cover or as shown in this manual Taps should be adjusted if necessary to match the available line voltage Any bolted electrical connections including taps should be checked and tightened since fasteners may have loosened during shipment Warning Fire Hazard Primary and secondary over current protection and conductor sizing must be in ac...

Page 6: ...y area where sound is objectionable TRANSFORMER LIFE Transformer life is dependent upon the thermal degradation of the insulation system which in turn is dependent upon the winding temperature and duration of operation at that Temperature Factors which affect transformer life are line voltage load current load cycle ambient temperature and other environmental conditions such as moisture corrosive ...

Page 7: ...7 ...

Page 8: ...8 ...

Page 9: ...9 ...

Page 10: ...10 ...

Page 11: ...11 ...

Page 12: ...12 ...

Page 13: ...13 ...

Page 14: ...14 ...

Page 15: ...15 ...

Page 16: ...16 ...

Page 17: ...17 ...

Page 18: ...HIS MANUAL FOLLOWING THESE PROCEDURES WILL RESULT IN SATISFACTORY PERFORMANCE WHEREAS DISREGARDING THEM CAN VOID THE WARRANTY The inspection for loose connections condition of terminal board overheating rust paint deterioration and general condition of the unit by a qualified service technician is recommended Corrective measures should be taken if necessary If there is a problem with your ProSafe ...

Page 19: ...imary and secondary circuits 2 Remove all fuses from the power source Additionally trip circuit breakers and take appropriate action to prevent the accidental resetting of the circuit breakers 3 Short out transformer secondaries before connecting and disconnecting equipment 4 To prevent potentially lethal high voltage current levels always connect a load to the secondary side of the transformer be...

Page 20: ...AL DAMAGES OF ANY KIND Some states do not allow the exclusion or limitation of consequential damages so the above limitations may not apply to you This warranty is made in lieu of all other obligations or liabilities on the part of Professional Mariner Professional Mariner neither assumes nor authorizes any person for any obligation or liability in connection with the sale of this product To make ...

Page 21: ...argers Battery Maintainers AC Plug Holders Battery Isolators ProSport Cup Holder Inverters Pro Inverters DC to AC Inverters Advanced Regulators Corrosion Control Products Waterproof Marine Binoculars Marine CCTV Color Camera Equipment Gold Plated Fuses and Holders A Complete Selection of Panel Meters and Shunts A Complete Line of Hand Held Test Meters Online Technical Support and Service Support V...

Reviews: