Rev 1.4 Page
6 of 14
Standard
Terminal
Designations
Proliphix
Terminal
Designations
Description
R, RH
RH
24VAC for W1 if RC used or all
HVAC contacts if RC not used
(see Table 3)
RC RC
24VAC for Y1, G if available (see
Table 3)
C C
(not
used)
W, W1
W1
Heat Relay
W2 W2
(Not
used)
Y, Y1
Y1
Cool Relay
Y2 Y2
(Not
used)
G G
Fan
Relay
- H
(Not
used)
Table 1 Terminal Conversion Chart
CAT5 Wiring for Ethernet Network
The inside label on the Base Plate provides several color coded wiring schemes for
Ethernet CAT5 connections. Match the label number to the Terminal block number for
CAT5 color coding as shown in Figure 3. If the other end of the CAT5 cable is
connected to a Proliphix EPA-60 Ethernet Power Adapter, follow the color coding for
T568A on the label.
Terminal
block
number
CAT5 T568A color code
1
White-Blue and Blue ends stripped and
twisted
2
White-Brown and Brown ends stripped and
twisted
3 White-Green
4 Green
5 White-Orange
6 Orange
Table 2 Ethernet CAT5 Wiring