Alarms Page
Internet Managed Thermostat Configuration Guide, Release 1.0
2-21
Part No. 600-03001-550, Rev. 1
Use
Table 2-5
to configure the
Alarms - Zone
page
fields.
Table 2-5 Alarms - Zone Field Descriptions
Field
Description
Zone Temperature Alarms
Low Temperature Limit
Select a value
or
Disabled
to indicate the low temperature
threshold detection status.
The value set by this parameter is monitored by the thermostat
and compared against the current
Zone Temperature
. If the
current
Zone Temperature
falls below this value, an alarm
condition is set and the status is displayed on the
HVAC (page
2-2)
page. In addition, this alarm is sent to the Proliphix web site
to trigger an e-mail notification, if the function is enabled, and
may also be sent as e-mail from this thermostat if configured on
Network - Notification Settings
page. See E-mail configuration
on
Network Notification Settings (page 2-42)
.
Disabled
(default) – No low temperature limit is set.
-30
°
F(-34.5
°
C) to 200
°
F(93
°
C)
This is a major (red) alarm condition.
Present for
Enter how long the condition must be in effect before the alarm
is triggered. Note that the default is 0 minutes and the maximum
time allowed is 240 minutes.
High Temperature Limit
Select a value or
Disabled
to indicate the high temperature
threshold detection status.
The value set by this parameter is monitored by the thermostat
and compared against the current
Zone Temperature
. If the
current
Zone Temperature
rises above this value, an alarm
condition is set and the status is displayed on the
HVAC (page
2-2)
page. In addition, this alarm is sent to the Proliphix web site
to trigger an e-mail notification, if the function is enabled, and
may also be sent as e-mail from this thermostat if configured on
Network - Notification Settings
page. See E-mail configuration
on
Network Notification Settings (page 2-42)
.
Disabled
(default) – No high temperature limit is set.
-30
°
F(-34.5
°
C) to 200
°
F(93
°
C)
This is a major (red) alarm condition.
Present for
Enter how long the condition must be in effect before the alarm
is triggered. Note that the default is 0 minutes and the maximum
time allowed is 240 minutes.