Connect to Solar Panel 

CAUTION: 

Before connecting to PV modules, please install 

separately 

a DC circuit breaker 

between inverter and PV modules. 

WARNING! 

All wiring must be performed by a qualified personnel. 

WARNING! 

It's very important for system safety and efficient operation to use appropriate 

cable for PV module connection. To reduce risk of injury, please use the proper 
recommended cable size as below. 

Typical Amperage 

Gauge 

Torque Value 

30A 

12 AWG 

1.4~1.6 Nm 

 
Step 1-

 Connect one cable to the positive (+) pole of solar panel and solar charger positive 

(+) terminal.   

Step 2- 

Connect the other cable to the negative (-) pole of solar panel and solar charger 

negative (-) terminal. 

Step 3- 

Check the solar charging indicator. If the LED lights up, it means that batteries are 

charged by solar power. When the batteries are fully charged or there is no solar power 
available, the LED will be off. (See following chart) 

 

PV Module Selection:

 

When selecting proper PV modules, please be sure to consider below requirements 
first:   

1.

 

Open circuit Voltage (Voc) of PV modules not exceeds max. PV array open circuit 
voltage of inverter.   

INVERTER MODEL 

1.2KVA 

2.4KVA 

Charging Current (PWM) 

30Amp 

System DC Voltage 

12Vdc 

24Vdc 

Operating Voltage Range 

15~18Vdc 

30~32Vdc 

Max. PV Array Open Circuit Voltage 

40Vdc 

60Vdc 

 
2.    Max. Power Voltage (Vmpp) of PV modules should be close to best Vmp of 

inverter or within Vmp range to get best performance. If one PV module cannot 

meet this requirement, it’s necessary to have several PV modules in series 
connection. Refer to below table. 

Model 

Best Vmp 

Vmp range 

1.2KVA 

15Vdc 

15V~18V 

2.4KVA 

30Vdc 

30V~32V 

Note:

 

* Vmp: panel max power point voltage.   

The PV charging efficiency is maximized while PV system voltage is close to 

Best Vmp. 

 

Maximum PV module numbers in Series: 

Vmpp of PV module * X pcs 

 

Best Vmp of Inverter or Vmp range 

PV module numbers in Parallel: 

Max. charging current of inverter / Impp 

Total PV module numbers = maximum PV module numbers in series * 
PV module numbers in parallel 

 
Take 1.2KVA inverter as an example to select proper PV modules. After considering 

Voc of PV module not exceeds 45Vdc and max. Vmpp of PV module close to 15Vdc or 
within 15Vdc ~ 18Vdc, we can choose PV module with below specification.   

Maximum Power (Pmax) 

85W 

Max. PV module numbers in series 

 17.6 x 1 

  15 ~ 18 

Max. Power Voltage Vmpp(V)  17.6V 
Max. Power Current Impp(A)  4.83A 

PV module numbers in parallel 

10 

 50 A / 4.83   

Total PV module numbers 

1 x 10 = 10 

Open Circuit Voltage Voc(V) 

21.6V 

Short Circuit Current Isc(A) 

5.03A 

Maximum PV module numbers in Series: 1 
PV module numbers in Parallel: 10 

Total PV module numbers: 1 x 10 = 10

 

 

Take 2.4KVA inverter as an example to select proper PV module. After considering 
Voc of PV module not exceed 60Vdc and max. Vmpp of PV module close to 30Vdc or 

within 30Vdc ~ 32Vdc, we can choose PV module with below specification.     
Maximum Power (Pmax) 

260W 

Max. PV module numbers in series 

 30.9 x 1 

  30 ~ 32 

Max. Power Voltage 
Vmpp(V) 

30.9V 

Max. Power Current 
Impp(A) 

8.42A 

PV module numbers in parallel 

 50 A / 8.42   

Total PV module numbers 

1 x 6 = 6 

Open Circuit Voltage 

Voc(V) 

37.7V 

Short Circuit Current Isc(A)  8.89A 

Maximum PV module numbers in Series: 1 

PV module numbers in Parallel: 6 
Total PV module numbers: 1 x 6 = 6 

Summary of Contents for IPS1200A

Page 1: ... The unit is designed for indoor use Do not expose this unit to rain snow or liquids of any type CAUTION To reduce risk of injury only use qualified batteries from qualified distributors or manufacturers Any unqualified batteries may cause damage and injury Do NOT use old or overdue batteries Please check the battery type and date code before installation to avoid damage and injury WARNING It s ve...

Page 2: ...ompartment CAUTION Use insulated tools to reduce the chance of short circuit when installing or working with the inverter the batteries or other equipments attached to this unit CAUTION For battery installation and maintenance read the battery manufacturer s installation and maintenance instructions prior to operating Personnel Precaution CAUTION Careful to reduce the risk or dropping a metal tool...

Page 3: ...e Please refer to Important Safety Warnings Section for the details Step 3 Tight the battery cables with the M5 nuts Do NOT place anything between the flat part of battery terminal and the battery cable ring terminal or overheating may occur See Fig 1 Step 4 Install a DC Breaker in a positive battery line The rating of the DC Breaker must be according to the inverter s battery current 75 Amp Keep ...

Page 4: ...connection Refer to below table Model Best Vmp Vmp range 1 2KVA 15Vdc 15V 18V 2 4KVA 30Vdc 30V 32V Note Vmp panel max power point voltage The PV charging efficiency is maximized while PV system voltage is close to Best Vmp Maximum PV module numbers in Series Vmpp of PV module X pcs Best Vmp of Inverter or Vmp range PV module numbers in Parallel Max charging current of inverter Impp Total PV module...

Page 5: ... Off Battery fully charged at power off and Off flashing every 11 sec Battery mode Battery weak and will flash every 2 second Sounding every 1 sec None weak battery Off Fault mode Fault code will be displayed Short fault F0 Overload fault F1 Battery bad F2 High output voltage F3 Main Relay Stick F4 Fan fault F5 Continuously sounding for 30 min and then alarm off The unit is overload The mark will ...

Page 6: ...nel Battery is not connected well Check the external battery cable and terminal Make sure all the battery connections to the unit are all correct Battery defect Replace the batteries Buzzer beeps continuously and red LED is on LCD display F0 Output short circuited Check if wiring is connected well and remove abnormal load LCD display F1 Overload error The inverter is loaded with more than 110 load...

Reviews: