![Project Fire Zonecheck Instruction Booklet Download Page 14](http://html1.mh-extra.com/html/project-fire/zonecheck/zonecheck_instruction-booklet_1614008014.webp)
11
Specifications
Zonecheck
Working Pressure Rating
Water, 12 bar (175 psi) maximum
Operating Temperature Range
0°C - 49°C (32°F – 120°F)
Pipe Diameter
50, 65, 80, 100mm (2, 2½ 3, 4”)
Approvals
LPCB, VdS, UL, FM *
Circulation Pump
Operating Voltage
1~230v 50Hz
Full Load Current
0.66 A
Power Rating
75 W maximum
IP Rating
IPX4D
Flow-switch
System Sensor
Type
WFDE
Contact Rating
10A @ 125/250 VAC; 2.5 A at 24 VDC
IP Rating
IP54
Triggering Flow-rate
30–57 l/min
Time Delay
0 - 30s
Flow-switch
Potter
Type
VSR-EU
Contact Rating
10A@125/250 VAC; 2.0Amps @ 30 VDC
IP Rating
IP54
Triggering Flow-rate
30-57 l/min (VdS); 15-38 l/min (UL)
Time Delay
0 - 30 s
Key-switch
Mounting
Flush-mounting
Type
ZCKYSE
Operating Voltage
Single-phase 230v 50Hz
Internal consumption
7.5 W maximum
Operation Modes
Self Test: Wired locally
Group Test: Interconnected
Standby (Ready State)
No LED
Test Initiation
‘Pump Running’ LED
Flow-switch Activation
‘Flow-switch Activated’ LED
Valve Fault
‘Valve Fault’ LED
Summary of Contents for Zonecheck