1-6 Parameter Descriptions
Parameter
Notation
Default
Value
Select parameters to be
locked
0 : No parameter
is locked
1 : Setup data are
locked
2 : Setup data and
User data except Set
point are locked
3 : All data are locked
LOCK
0
Parameter Description
Range
0
1
2
3
4
5
6
:
:
:
:
:
:
:
T type thermocouple
E type thermocouple
B type thermocouple
R type thermocouple
S type thermocouple
J type thermocouple
K type thermocouple
7
13
8
14
9
10
11
12
N type thermocouple
L type thermocouple
PT 100 ohms DIN
curve
PT 100 ohms JIS
curve
4 - 20 mA linear
current input
0 - 20 mA linear
current input
0 - 1V linear voltage
input
:
:
:
:
:
:
:
:
0 - 60 mV linear
millivolt input
INPT
Input sensor selection
1
(0)
SP2
Set point for output 2
when output 2 performs
alarm function
Low: -19999 High :45536
10.0 C
(18.0 F)
SP1
Set point for output 1
Low: SP1L High :SP1H
25.0 C
(77.0 F)
SP3
Set point for alarm or
dwell timer output
Low: -19999 High: 45536
10.0 C
(18.0 F)
15
16
17
0 - 5V linear voltage
input
1 - 5V linear voltage
input
0 - 10V linear voltage
input
:
:
:
NOTE;
Input Selection
11 - 17
of Linear (ma/VDC)
Require
special order
only See Matrix
Page 8.
12