30
FAULT
PROBABLE
CAUSE
ACTION
REQUIRED
14.
Abnormal
Noise
in
Compressor
(*)
Bolts
loose.
Tighten
bolts
Fluid
in
suction
line
Check
and
re-set
thermostatic
expansion
valves.
Check
that
the
liquid
solenoid
valves
do
not
remain
open
when
machine
stops.
Bulb
is
loose
or
incorrectly
positioned.
Check
bulb
position
Emulsion
in
oil
crankcase
Incorrect
lubrication.
See
paragraphs
13
and
10.
15.
The
Compressor
Motor
does
not
start
Low
pressure
switch
cuts
out.
See
paragraph
3.
High
pressure
switch
cuts
out.
See
paragraph
6.
Fuses
burnt
out
Check
the
cause
and
change
fuses
Anti-short
cycle
time
delay
relay
is
in
operation
Wait
Internal
security
switched
out.
Check
cause
of
increase
in
motor
winding
temperatures
(re-set
times
06:00
to
24:00).
Main
circuit
breaker
switch
open.
Close
circuit-breaker.
16.
The
Compressor
works
continuously
Control
system
or
other
automatic
device
fault.
See
paragraphs
12
and
13.
Installation
insufficiently
charged
Charge
installation
with
refrigerant
Evaporators
blocked
or
ice
present
Clean
and
defrost
evaporators
(*)If
there
is
an
abnormal
noise
in
the
compressor,
switch
off
the
compressor.
Find
the
cause
of
the
noise
and
remedy
before
re-starting
Manufactured
in
France
by
PROFROID
CARRIER
S.
C.
S
178,
rue
du
Fauge
-
ZI
Les
Paluds
-
B.P.
1152
-
13782
Aubagne
Cedex
-
France
International:
Tel.
(33)
4
42
18
05
00
-
Fax
(33)
4
42
18
05
02
Summary of Contents for QUIETOR GQH-GQL
Page 51: ...48 e ct d ROl...